6 - 3 6 - 3
MELSEC
6 PARAMETER SETTINGS
: Setting required : Setting not required
Description
Master
station
Local station
Standby
master station
Reference
section
Setting item
Station information Settings
14) All connect count
Set the number of slave stations connected to the
master station. (Including reserved stations)
Setting range: 1 to 64 (Default: 64)
----
Station information
15) Station
type
1
Set the type of the relevant station.
Setting range: Ver.1 remote I/O station (Default)
Ver.1 remote device station
Ver.1 intelligent device station
Ver.2 remote device station
Ver.2 intelligent device station
Refer to
Table
6.2
----
16) Expanded
cyclic
Make the expanded cyclic setting of the relevant station.
(Can be set in remote net ver.2 mode or remote net
additional mode)
Setting item: single (Default), double, quadruple,
octuple
Section
4.4.7
17) Occupied
Sta.
Set the number of stations occupied by the relevant
station.
Setting item: occupies 1 station (Default), occupies
2 stations, occupies 3 stations,
occupies 4 stations
----
18) Remote
station points
Set the points of the relevant station.
Setting range: 0 points (Default), 8 points, 8 8
points, 16 points, 32 points
Section
4.4.6
19) Reserve/
Invalid
station select
Specify the reserved station or error invalid station.
Setting range: No setting (Default), Reserved station,
Invalid station
Section
4.4.1
Section
4.4.2
20) Intelligent
buffer select
(word)
Assign the buffer memory size for transient transmission
to the local station, the intelligent device station and the
standby master station.
Setting range (Per station)
Send/receive buffer size:
0, 64 to 4096 (words) (Default: 64)
Note that, when it is set to multiple stations, the
total send/receive buffer size for all slave stations
must be within 4096 (words).
Automatic (automatic update) buffer size:
0, 64 to 4096 (words) (Default: 128)
Note that, when it is set to multiple stations, the
total automatic buffer size for all slave stations
must be within 4096 (words).
----
1: Select the intelligent device station when using the local station.
POINT
When changing parameters and/or settings of the master station or slave station,
perform the operation after stopping the data link at the master station.
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......