4 - 44 4 - 44
MELSEC
4 FUNCTIONS
4.4.6 Reducing the reserved points of the remote I/O stations (Remote I/O station points
setting)
The points of each remote I/O station can be set to 8, 16 or 32 points.
Therefore, only the points used for I/O need to be allocated for the remote devices in
the CC-Link system and unused points can be reduced. It is effective for saving device
points.
The remote I/O station points setting can be used in the remote net ver.2 mode only.
Station
number 2
Remote output RY
Y07 to Y00
Y07 to Y00
Y0F to Y00
Y0F to Y00
Y1F to Y10
8-point output module
Device area when remote I/O points setting is made
Device area when remote I/O points setting is not made
8-point output module
16-point output module
32-point output module
Personal
computer
Master station
Station number 3
Station
number 4
to
Station
number 1
Remote I/O station
(Station number 1:
Occupies 1 station)
Remote I/O station
(Station number 2:
Occupies 1 station)
Remote I/O station
(Station number 3:
Occupies 1 station)
Remote I/O station
(Station number 4:
Occupies 1 station)
mdSend
Program
POINT
(1) Set points to even-numbered 8-point setting remote I/O stations consecutively.
If points are set to odd-numbered 8-point setting remote stations, select "8
8 points reserved" in the "remote station points" setting of the last of
the consecutive remote I/O stations.
Remote output RY
8-point output module
Master station
to
Remote I/O station
(Station number 1:
Occupies 1 station)
Station
number 2
8points
(reserved)
Remote I/O station
(Station number 2:
Occupies 1 station)
Remote I/O station
(Station number 3:
Occupies 1 station)
Remote I/O station
(Station number 4:
Occupies 1 station)
8-point output module
8-point output module
32-point output module
Y0F to Y00
Y1F to Y10
Y07 to Y00
Y07 to Y00
Y07 to Y00
Station
number 1
Station
number 3
reserved
Station
number 4
Odd-numbered 8-point setting remote stations cannot be set for 8 remote
station points.
Remote output RY
8-point output module
Master station
to
Remote I/O station
(Station number 1:
Occupies 1 station)
Station
number 2
Cannot be set.
Remote I/O station
(Station number 2:
Occupies 1 station)
Remote I/O station
(Station number 3:
Occupies 1 station)
Remote I/O station
(Station number 4:
Occupies 1 station)
8-point output module
8-point output module
32-point output module
Y0F to Y00
Y1F to Y10
Y07 to Y00
Y07 to Y00
Y07 to Y00
Station
number 1
Station
number 3
Station number 4
Refer to Section 8.2.5 for parameter setting.
[Setting method]
The setting is performed at <<Parameter settings>> in the CC-Link Ver.2 utility.
Refer to Section 8.2.5 for setting details.
(1) Precautions for remote I/O station points setting
Set the points not less than I/O points of the actually installed remote I/O station
with the parameter. Otherwise, the I/O operations corresponding to the exceeded
points will not function normally.
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......