4 - 28 4 - 28
MELSEC
4 FUNCTIONS
(2) Setting method
The setting is performed at <<Parameter settings>> in the CC-Link Ver.2 utility.
Refer to Section 8.2.5 for details.
(a) Setting the master station
1) Set the "Sta.No." and "Type" in <<Parameter settings>>.
Sta.No.: 0
Type: Master
station
2) Set the "Standby master station" with the Other settings button.
Setting range: 1 to 64 (No standby master station specified for blank)
Default:
0 (No standby master station specified)
3) Select the "Ver.1 Intelligent device station" or "Ver.2 Intelligent device
station" for "Type" of the station information.
Make a selection according to the mode set in "Mode setting".