5 - 14 5 - 14
MELSEC
5 PROCEDURE BEFORE STARTING THE DATA LINK
5.5 Station Number Setting
The following explains how to set the station numbers for the master station, local
station, standby master station, remote station and intelligent device station.
For details on the station number settings, refer to Section 8.2.3.
Specify the station numbers according to the following conditions:
(1) Assign sequential station numbers.
Station numbers can be specified regardless of the order in which the stations are
connected.
For a module occupying two or more stations, specify the first station number.
(2) Specify unused station numbers as reserved stations.
If unused station numbers are not specified as reserved stations, they will be
handled as data link faulty stations (can be checked with special link registers
SW0080 to SW0083).
(3) Specify unique station numbers.
If duplicate station numbers are specified, an installation error occurs. (Error
codes are stored in SW0069)
[Setting example] One station was skipped when station numbers were specified.
St. No. 4
5) Local station
3) Standby master station
2) Remote device station
1) Remote
I/O station
Data link faulty station
(If this station was specified as a reserve station,
it would not have been treated as a faulty station.)
1)
Remote I/O station
(occupies 1 station)
2) Remote device
station
(occupies 2 stations)
Master
station
3)
Standby
master station
(occupies
4 stations)
5)
Local station
(occupies
1 station)
4) Intelligent
device station
(occupies 1 station)
Station
number "0"
Intelligent
device
station
4)
Station
number "1"
Station
number "2"
Station
number "5"
Station
number "9"
Station
number "10"
St. No. 3
St. No. 2
St. No. 1
St. No. 5
St. No. 6
St. No. 7
St. No. 8
St. No. 9
St. No. 10
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......