App - 86 App - 86
MELSEC
APPENDIX
(b) Immunity requirements
Standard
Test item
Test description
Value specified in standard
EN61131-2:
2007
EN61000-4-2
Electrostatic discharge immunity
*1
An electrostatic discharge is
applied to the enclosure of the
equipment.
• 8kV Air discharge
• 4kV Contact discharge
EN61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity
*1
An electric field is radiated to the
product.
80% AM modulation @1kHz
• 80 to 1000MHz: 10V/m
• 1.4 to 2.0GHz: 3V/m
• 2.0 to 2.7GHz: 1V/m
EN61000-4-4
Fast transient burst
immunity
*1
Burst noise is applied to power
lines and signal lines.
• AC/DC power, I/O power, and AC I/O
(unshielded) lines: 2kV
• DC I/O, analog, and communication
lines : 1kV
EN61000-4-5
Surge immunity
*1
Lightning surge is applied to
power lines and signal lines.
• AC power, AC I/O power, and AC I/O
(unshielded) lines: 2kV CM, 1kV DM
• DC power and DC I/O power lines:
0.5kV CM, 0.5kV DM
• DC I/O, AC I/O (shielded), analog,
and communication lines: 1kV CM
EN61000-4-6
Conducted RF immunity
*1
High-frequency noise is applied
to power lines and signal lines.
0.15 to 80MHz, 80% AM modulation
@1kHz, 10Vrms
EN61000-4-8
Power-frequency magnetic
field immunity
*1
The product is immersed in the
magnetic field of an induction
coil.
50/60Hz, 30A/m
EN61000-4-11
Voltage dips and interruption
immunity
Power voltage is momentarily
interrupted.
• 0%, 0.5 period, starting at
zerocrossing
• 0%, 250/300 period (50/60Hz)
• 40%, 10/12 period (50/60Hz)
• 70%, 25/30 period (50/60Hz)
1: The tests were conducted installed in a control panel.
Содержание Q80BD-J61BT11N
Страница 2: ......
Страница 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Страница 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Страница 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Страница 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Страница 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Страница 212: ...13 12 13 12 MELSEC 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT R2 MEMO ...
Страница 228: ...14 16 14 16 MELSEC 14 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATION AJ65BT D75P2 S3 MEMO ...
Страница 354: ...App 92 App 92 MELSEC APPENDIX Appendix 19 2 Q81BD J61BT11 121 141 147 153 19 158 103 5 91 Unit mm ...
Страница 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Страница 361: ......