Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-151-
Function
code
Name
Description
Setting
range
Default Modify
switching
P03.03
Speed-loop proportional
gain 2
0
–200.0
0
–200.0
20.0
○
P03.04
Speed-loop integral time 2 0.000
–10.000s
0.000
–
10.000
1.000s
○
P03.05
High-point frequency for
switching
P03.02
–P00.03 (Max. frequency)
P03.02
–
P00.03
10.00Hz
○
P03.06
Speed-loop output filter
0
–8
(corresponding
to
0
–
2
8
/10ms)
0
–8
0
○
P03.07
Electromotive slip
compensation coefficient of
vector control
50%
–200%
50
–200
100%
○
P03.08
Braking slip compensation
coefficient of vector control
50%
–200%
50
–200
100%
○
P03.09
Current-loop proportional
coefficient P
0
–65535
0
–65535
1000
○
P03.10
Current-loop integral
coefficient I
0
–65535
0
–65535
1000
○
P03.11
Torque setting method
0: Torque control invalid
1: Keypad (P03.12)
2: AI1 (100% corresponding to
three times the motor rated
current)
3: AI2 (Same as the above)
4: AI3 (Same as the above)
5: Pulse frequency HDI (Same
as the above)
6: Multi-step torque (same as the
above)
7: MODBUS communication
(same as the above)
8: PROFIBUS/CANopen
communication (same as the
above)
9: Ethernet communication
(same as the above)
10: Reserved
0
–10
0
○
P03.12
Torque set through keypad
-300.0%
–300.0% (of the motor
rated current)
-300.0
–
300.0
50.0%
○
P03.13
Torque reference filter time 0.000
–10.000s
0.000
–
10.000
0.100s
○
P03.14
Setting source of forward
rotation upper-limit
frequency in torque control
0: Keypad (P03.16)
1: AI1
2: AI2 (same as the above)
3: AI3 (same as the above)
4: Pulse frequency HDI
5: Multi-step setting (same as the
0
–9
0
○