Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-159-
Function
code
Name
Description
Setting
range
Default Modify
P05.39
AI2 middle value
P05.37
–P05.41
P05.37
–
P05.41
0.00V
P05.40
Corresponding setting of AI2
middle value
-100.0%
–100.0%
-100.0
–
100.0
0.0%
P05.41
AI2 upper limit
P05.39
–10.00V
P05.39
–
10.00
10.00V
○
P05.42
Corresponding setting of AI2
upper limit
-100.0%
–100.0%
-100.0
–
100.0
100.0%
○
P05.43
AI2 input filter time
0.000s
–10.000s
0.000
–
10.000
0.100s
○
P05.44
AI3 lower limit
0V
–P05.46
0
–P05.46
0.00V
○
P05.45
Corresponding setting of AI3
lower limit
-100.0%
–100.0%
-100.0
–
100.0
-100.0%
○
P05.46
AI3 middle value
P05.44
–P05.48
P05.44
–
P05.48
5.00V
○
P05.47
Corresponding setting of AI3
middle value
-100.0%
–100.0%
-100.0
–
100.0
0.0%
○
P05.48
AI3 upper limit
P05.46
–10.00V
P05.46
–
10.00
10.00V
○
P05.49
Corresponding setting of AI3
upper limit
-100.0%
–100.0%
-100.0
–
100.0
100.0%
○
P05.50
AI3 input filter time
0.000s
–10.000s
0.000
–
10.000
0.100s
○
P05.51
HDI high-speed pulse input
function selection
0: Input set through frequency
1
–2: Reserved
0
0
◎
P05.52
HDI lower limit frequency 0.00kHz
–P05.54
0.00
–P05.54 0.00kHz
○
P05.53
Corresponding setting of
HDI lower limit frequency
-100.0%
–100.0%
-100.0
–
100.0
0.0%
○
P05.54
HDI upper limit frequency P05.52
–50.00kHz
P05.52
–
50.00
50.00kHz
○
P05.55
Corresponding setting of
HDI upper limit frequency
-100.0%
–100.0%
-100.0
–
100.0
100.0%
○
P05.56
HDI frequency input filter
time
0.000s
–10.000s
0.000
–
10.000
0.100s
○
P06 group
––Output terminals
P06.00
HDO output type
0: Open collector high-speed
pulse output
1: Reserved
0
–1
0
◎
P06.01
Y1 output
0: Invalid
1: Running
2: Running forward
3: Running reversely
4: Jogging
5: VFD in fault
6: Frequency level detection
FDT1
7: Frequency level detection
0
–30
0
○
P06.02
HDO output
0
–30
0
○
P06.03
Relay RO1 output
0
–30
1
○
P06.04
Relay RO2 output
0
–30
5
○
P06.05
Relay RO3 output
0
–30
0