Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-27-
Function
code
Name
Description
Setting range
Default
entry point
0: Invalid
1: Valid
P03.25
Overmodulation entry
point
0.0
–100.0% (modulation degree)
0.0
–100.0%
90.0%
P03.26
Overmodulation
proportional coefficient
P
0.001
–60.000
0.001
–60.000
5.000
P03.27
Overmodulation
integral coefficient I
0.01
–30.000
0.01
–30.000
5.00
P03.28
Phase-lock loop
integral
0
–10
0
–10
10
P03.29
Reserved
P03.30
Enabling high grid
voltage
0: Disable
1: Enable
0
–1
P03.31
High grid voltage
adjustment Kp
0
–10
0
–10
0.2
P03.32
High grid voltage
adjustment Ki
0
–100
0
–100
4
P03.33
PLL impedance
adjustment coefficient
0.00
–5.00
0.00
–5.00
0
P03.34
–
P03.35
Reserved
P03.36
Rectifier phase shifting
compensation angle
The function code is used to
compensate the phase angle of
phase lock. A positive value
indicates that the phase-locked
angle is shifted right by the angle set
by the function code, while a
negative value indicates the
phase-locked angle is shifted left.
(Valid only for the six-pulse rectifier)
-30
–+30
0
P03.37
Upper limit of voltage
hysterisis
Bus voltage judgment hysteresis
upper limit V_ZH = Input voltage
(P08.06)*1.414 + P03.37;
When the actual bus voltage is
greater than V_ZH, the IGBT
feedback enabling angle starts to
increase slowly until it reaches 120
degrees.
When the actual bus voltage is less
than V_ZL (see P28.05), the IGBT
feedback enabling angle starts to
decrease slowly until it reaches the
lower limit (see P03.38).
(Valid only for the six-pulse rectifier)
-800.0
–300.0
30.0V
P03.38
IGBT feedback
enabling angle
During six-pulse rectifier mode, the
feedback angle can be set through
0
–120
100°