Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-22-
The running commands are controlled through keypad keys, such as the RUN and STOP/RST keys.
1: Terminal (“LOCAL/REMOT” indicator blinking)
The running commands are controlled through multi-function input terminals.
2: Communication (“LOCAL/REMOT” indicator on)
The running commands are controlled by the upper computer in communication mode.
Function
code
Name
Description
Setting range
Default
P00.02
Communication
mode of running
commands
0: RS485
1: PROFIBUS
2: Ethernet
3: CANopen
4
–6: Reserved
0
–6
0
The function code is used to select the mode that PWM rectifier controls communication commands.
Note: The options 1, 2, and 3 are add-on functions and are available only when corresponding expansion cards
are configured.
Function
code
Name
Description
Setting range
Default
P00.03
Running mode
0: COSφ
1
–2: Reserved
0
–2
0
The function code is used to select the running mode of the PWM rectifier.
0: COSφ mode. The reactive current is determined by the power factor.
Note: The mode 0 has voltage loop and the parameters in P03 group should be set for mode 0.
Function
code
Name
Description
Setting range
Default
P00.04
DC bus voltage setting
method
0: Automatic
1: Keypad
2: Reserved
0
–2
1
P00.05
DC bus voltage setting 300.0
–2100.0V
300.0
–2100.0
Model
depended
When P00.04=1, P00.05 is set through the keypad.
Mapping between voltages and DC bus voltages
Model
Factory default DC bus voltage
(P00.05)
Overvoltage point
660V
1050V
1200V
1140V
1850V
2150V
3300V
5000V
6000V
Function
code
Name
Description
Setting range
Default
P00.08
Resonance
suppression factor
0
–10
0
–10
0
Function
code
Name
Description
Setting range
Default
P00.09
Overmodulation
selection
0: Disable
1: Enable
0
–1
1