Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-89-
Function
code
Name
Description
Setting range
Default
P05.54
HDI upper limit frequency P05.52
–50.00kHz
P05.52
–50.00
50.00kHz
P05.55
Corresponding setting of
HDI upper limit frequency
-100.0%
–100.0%
-100.0
–100.0
100.0%
P05.56
HDI frequency input filter
time
0.000s
–10.000s
0.000
–10.000
0.100s
The function codes define the corresponding relations when the pulse is the setting input. It is similar to AI functions
(P05.32
–P05.50).
P06 group
—Output terminals
Function
code
Name
Description
Setting range
Default
P06.00
HDO output type
0: Open collector high-speed pulse
output
1: Reserved
0
–1
0
P06.01
Y1 output
0: Invalid
1: Running
2: Running forward
3: Running reversely
4: Jogging
5: VFD in fault
6: Frequency level detection FDT1
7: Frequency level detection FDT2
8: Frequency reached
9: Running at 0Hz
10: Upper limit frequency reached
11: Lower limit frequency reached
12: Ready for running
13: Pre-exciting
14: Overload pre-alarm
15: Underload pre-alarm
16: Simple PLC stage completed
17: Simple PLC cycle completed
18: Reserved
19: Reserved
20: External fault is valid
21: Reserved
22: Running time reached
23: Modbus communication virtual
terminal output
24: PROFIBUS/CANopen
communication virtual terminal output
25: Ethernet communication virtual
terminal output
26: DC bus voltage established
27
–28: Reserved
29: Motor OH pre-alarm
30: Phase-locked and synchronous
output at power frequency
0
–30
0
P06.02
HDO output
0
–30
0
P06.03
Relay RO1 output
0
–30
1
P06.04
Relay RO2 output
0
–30
5
P06.05
Relay RO3 output
0
–30
0