Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-79-
Function
code
Name
Description
Setting
range
Default
P04.16
V/F frequency point 1 of
motor 2
0.00Hz
–P04.18
0.00
–
P04.18
0.00Hz
P04.17
V/F voltage point 1 of
motor 2
0.0%
–110.0% (of the rated voltage of
motor 2)
0.0
–110.0
0.0%
P04.18
V/F frequency point 2 of
motor 2
P04.16
–P04.20
P04.16
–
P04.20
0.00Hz
P04.19
V/F voltage point 2 of
motor 2
0.0%
–110.0% (of the rated voltage of
motor 2)
0.0
–110.0
0.0%
P04.20
V/F frequency point 3 of
motor 2
P04.18
–P12.02 (Rated frequency of
motor 2)
or P04.18
–P12.16 (Rated frequency of
motor 2)
P04.18
–
P12.02
or P04.18
–
P12.16
0.00Hz
P04.21
V/F voltage point 3 of
motor 2
0.0%
–110.0% (of the rated voltage of
motor 2)
0.0
–110.0
0.0%
P04.22
V/F slip compensation
gain of motor 2
0.0
–200.0%
0.0
–200.0
100.0%
P04.23
Low-frequency
oscillation control factor
of motor 2
0
–100
0
–100
10
P04.24
High-frequency
oscillation control factor
of motor 2
0
–100
0
–100
10
P04.25
Oscillation control
threshold of motor 2
0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
–
P00.03
30.00Hz
The function codes define the V/F setting method of motor 2 to meet the needs of different loads. For details, see P04.13
–
P04.25.
Note: P04 group includes V/F parameters of four motors which can be displayed simultaneously and will be valid
to the selected motor. The motor can be selected by the channels defined in the function code P08.31.
Function
code
Name
Description
Setting range
Default
P04.26
Energy-saving run
0: Disable
1: Automatic energy-saving run
0
–1
0
The function code is used to enable an energy-saving run. In light-load state, the motor can adjust the output voltage
automatically to achieve energy saving.
Function
code
Name
Description
Setting range
Default
P04.27
Voltage setting
channel
0: Keypad (The output voltage is
determined by P04.28.)
1: AI1
2: AI2
3: AI3
4: HDI
5: Multi-step speed running (The setting
is determined by group P10.)
6: PID
0
–10
0