Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-37-
Function
code
Name
Description
Setting range
Default
29: IGBT overheat fault (OH1)
30: Phase-U Vce check fault (Out1)
31: Phase-V Vce check fault (Out2)
32: Phase-W Vce check fault (Out3)
Pre-alarm type:
05: IGBT temperature pre-alarm
(A-vH1)
For details, see fault information.
Function
code
Name
Description
Setting range
Default
P10.06
Input terminal status
at present fault
0x0
–0xF
0x0
–0xF
0x0
The function code is used to record the input terminal status when the present fault occurs.
Function
code
Name
Description
Setting range
Default
P10.07
Output terminal status
at present fault
0x0
–0xF
0x0
–0xF
0x0
The function code is used to record the output terminal status when the present fault occurs.
Function
code
Name
Description
Setting range
Default
P10.08
DC voltage at present
fault
0.0
–6000.0V
0.0
–6000.0
0.0V
The function code is used to record the DC voltage when the present fault occurs.
Function
code
Name
Description
Setting range
Default
P10.09
Grid voltage at
present fault
0.0
–4000.0V
0.0
–4000.0
0.0V
The function code is used to record the grid voltage when the present fault occurs.
Function
code
Name
Description
Setting range
Default
P10.10
Input current at
present fault
0.0
–6000.0A
0.0
–6000.0
0.0A
The function code is used to record the input current when the present fault occurs.
Function
code
Name
Description
Setting range
Default
P10.13
Max. IGBT
temperature at
present fault
-20.0
–120.0°C
-20.0
–120.0
0.0°C
The function code is used to record the IGBT temperature when fault occurs and display 3PH IGBT temperature at no
fault.
Function
code
Name
Description
Setting range
Default
P10.22
Input terminal status
at last fault
0x0
–0xF
0x0
–0xF
0x0