Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-70-
Function
code
Name
Description
Setting range
Default
P02.04
Rated voltage of AM
1
0
–4000V
0
–4000
Model
depended
P02.05
Rated current of AM 1 0.8
–6000.0A
0.8
–6000.0
Model
depended
The function codes are used to set the parameters for the controlled AM.
To ensure the control performance, set P02.01
–P02.05 correctly according to the information on the nameplate of the AM.
The VFD provides the parameter autotuning function. Whether parameter autotuning can be performed properly depends
on the settings of the motor nameplate parameters.
In addition, you need to configure a motor according to the standard motor configuration of the VFD. If the power of the
motor is greatly different from that of the standard motor configuration, the control performance of the VFD degrades
significantly.
Note: Resetting the rated power of the motor (P02.01) can initialize the parameters P02.02
–P02.10.
Function
code
Name
Description
Setting range
Default
P02.06
Stator resistance of
AM 1
0.001
–65.535Ω
0.001
–65.535
Model
depended
P02.07
Rotor resistance of
AM 1
0.001
–65.535Ω
0.001
–65.535
Model
depended
P02.08
Leakage inductance
of AM 1
0.1
–6553.5mH
0.1
–6553.5
Model
depended
P02.09
Mutual inductance of
AM 1
0.1
–6553.5mH
0.1
–6553.5
Model
depended
P02.10
No-load current of
AM 1
0.1
–6553.5A
0.1
–6553.5
Model
depended
Note: Do not modify these parameters unless it is necessary.
After motor parameter autotuning is properly performed, the values of P02.06
–P02.10 are automatically updated. These
parameters are the benchmark parameters for high-performance vector control, directly affecting the control performance.
Function
code
Name
Description
Setting range
Default
P02.11
Magnetic saturation
coefficient 1 of iron
core of AM 1
0.0
–100.0%
0.0
–100.0
80.0%
P02.12
Magnetic saturation
coefficient 2 of iron
core of AM 1
0.0
–100.0%
0.0
–100.0
68.0%
P02.13
Magnetic saturation
coefficient 3 of iron
core of AM 1
0.0
–100.0%
0.0
–100.0
57.0%
P02.14
Magnetic saturation
coefficient 4 of iron
core of AM 1
0.0
–100.0%
0.0
–100.0
40.0%
The function codes indicate the magnetic saturation coefficients of AM in flux-weakening control.
Function
code
Name
Description
Setting range
Default
P02.15
Rated power of SM 1 0.1
–3000.0kW
0.1
–3000.0
Model
depended