Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-24-
Main contactor
switch on
Bus voltage raises
Switch on of the
buffer contactor
Power on of the
main circuit
Main contactor switch on?
Keypad displays tbE
N
Y
Buffer contactor
switch off
P01.01=1
Ready
Function
code
Name
Description
Setting range
Default
P01.02
Undervoltage setting
value of input voltage
75.0
–95.0%
75.0
–95.0
85.0%
P01.03
Overvoltage setting
value of input voltage
105.0
–125.0%
105.0
–125.0
115.0%
Function
code
Name
Description
Setting range
Default
P01.06
Auto-running wait
time
0
–3600.0s
0
–3600.0
0.0s
When P01.06 is set to 0.0s, automatic running is invalid.
When P01.06 is set to a value but not 0.0s: the system will lock phase after power on. The system will operate
automatically if it locks phase and detects successfully.
The automatic running function is valid only when power on. If fault occurs, the function will be invalid automatically and
the system will stop. And after that, the system will be started manually. The function will be enabled if power on again.
Note: Regardless of whether automatic running is valid, the diode rectifier mode is always valid, and the DC bus
is always live.
Function
code
Name
Description
Setting range
Default
P01.07
Delay of auto fault reset
0.0
–3600.0s
0.0
–3600.0
1.0s
P01.08
Auto fault reset count
0
–10
0
–10
0
When P01.08 is 0, automatic fault reset is invalid.
When P01.08 is not 0, automatic fault reset is valid and is performed after the time specified by P01.07. Fault reset is
invalid for EF, dIS, PC_T1, OH1, OUT1, OUT2, and OUT3.
Note: A fault is reported when the successive reset count exceeds the count specified by P01.08.