Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-164-
Function
code
Name
Description
Setting
range
Default Modify
BIT14:
Motor
overload
percentage (% on)
BIT15: VFD overload percentage
(% on)
Bit 6: Ramp frequency reference
(Hz on)
BIT7: Reserved
BIT8: Reserved
Bit 9
–15: Reserved
P07.07
Selection of parameters to
be displayed in the stop
state
0x0000
–0xFFFF
BIT0: Set frequency (Hz on,
blinking slowly)
BIT1: Bus voltage (V on)
BIT2: Input terminal state
BIT3: Output terminal state
BIT4: PID reference value (%
blinking)
BIT5: PID feedback value (% on)
BIT6: Set torque (% on)
BIT7: AI1 (V on)
BIT8: AI2 (V on)
BIT9: AI3 (V on)
BIT10: HDI frequency
BIT11: PLC and actual step of
multi-step speed
BIT12: Reserved
BIT13: Reserved
BIT14
–BIT15: Reserved
0x0000
–
0xFFFF
0x00FF
○
P07.08
Frequency display
coefficient
0.01
–10.00
0.01
–10.00
1.00
○
P07.09
Rotational speed display
coefficient
0.1
–999.9%
0.1
–999.9
100.0%
○
P07.10
Linear speed display
coefficient
0.1
–999.9%
0.1
–999.9
1.0%
○
P07.11 Rectifier bridge temperature 0
–100.0
℃
●
P07.12 Inverter module temperature 0
–100.0
℃
●
P07.13
DSP version number
1.00
–655.35
●
P07.14
Local accumulative running
time
0
–65535h
●
P07.15
VFD electricity consumption
high-order bits
0
–65535kWh (*1000)
●
P07.16
VFD electricity consumption
low-order bits
0.0
–999.9kWh
●
P07.17
Reserved
P07.18
VFD rated power
0.4
–3000.0kW
●
P07.19
VFD rated voltage
0
–4000V
●
P07.20
VFD rated current
0.1
–6000.0A
●