Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-148-
Function
code
Name
Description
Setting
range
Default Modify
P00.17
Reserved
◎
P00.18
Function parameter restore
0: No operation
1: Restore default values
2: Clear fault records
0
–2
0
◎
P01 group
––Start and stop control
P01.00
Start mode
0: Direct start
1: Start after DC braking
2: Start after rotating speed
tracking
0
–2
0
◎
P01.01
Starting frequency of direct
start
0.00
–50.00Hz
0.00
–50.00 0.50Hz
◎
P01.02 Starting frequency hold time 0.00
–50.00s
0.0
–50.00
0.00s
◎
P01.03
Braking current before start
0.0
–100.0% (of the VFD rated
current)
0.0
–100.0
0.0%
◎
P01.04
Braking time before start
0.00
–50.00s
0.00
–50.00
0.00s
◎
P01.05
ACC/DEC mode
0: Linear
1: S curve
0
–1
0
◎
P01.06
S curve starting segment
proportion
0.0
–50.0% (ACC/DEC time)
0.0
–50.0
30.0%
◎
P01.07
S curve ending segment
proportion
0.0
–50.0% (ACC/DEC time)
0.0
–50.0
30.0%
◎
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
–1
0
○
P01.09
Starting frequency of DC
braking for stop
0.00
–P00.03
(Max.
output
frequency)
0.00
–P00.03 0.00Hz
○
P01.10
Wait time before DC braking
for stop
0.00
–50.00s
0.00
–50.00
0.00s
○
P01.11
DC braking current for stop
0.0
–100.0% (of the VFD rated
current)
0.0
–100.0
0.0%
○
P01.12
DC braking time for stop
0.00
–50.00s
0.00
–50.00
0.00s
○
P01.13
FWD/REV running
deadzone time
0.0
–3600.0s
0.0
–3600.0
0.0s
○
P01.14
FWD/REV running switching
mode
0: Switch at zero frequency
1:
Switch
at
the
starting
frequency
2: Switch after the speed
reaches the stop speed with a
delay
0
–2
0
◎
P01.15
Stop speed
0.00
–100.00Hz
0.00
–100.0 0.50 Hz
◎
P01.16
Stop speed detection mode
0: Detect by the speed setting
(without speed delay)
1: Detect by speed feedback
(valid only for vector control)
0
–1
0
◎
P01.17
Feedback speed detection
time
0.00
–100.00 s (valid when
P01.16=1)
0.00
–100.0
0.50s
◎
P01.18
Terminal-based running
command protection at
0: The terminal running
command is invalid at power-on
0
–1
0
○