Goodrive3000 series medium voltage VFD
PROFIBUS communication
-223-
VFD SW
Bit
Value
Name
Status/description
11
1
MASTER MODE
Master mode in master/slave control.
0
Not master mode.
12
1
SLAVE MODE
Slave mode in master/slave control.
0
Not slave mode.
13
1
TORQUE CONTROL
Torque control mode
0
Speed control mode
14
1
MOTO GROUP FEEDBACK-2 Bit 3 and Bit 14 determine which motor is selected.
0
15
Reserved
Actual value (ACT): The second to twelfth words (PZD2
–PZD12) in a PZD task packet from the rectifier unit are the main
actual values.
Table 9-11 Actual value of the rectifier unit
Bit
Name
function selection
Sent PZD2 0: Disable
1: DC voltage (* 10, V)
2: DC voltage feedback (* 10, V)
3: Input voltage valid value (* 10, V)
4: Input current valid value (* 10, A)
5: Input power (* 10, kW)
6: Input power factor (*100)
7: Grid frequency (* 10, Hz)
8: Active current feedback (100% corresponds to the
rectifier rated current.)
9: Reactive current feedback (100% corresponds to
the rectifier rated current.)
10: Fault code
11: AI1 input (*100, V)
12: AI2 input (*100, V)
13: Reserved
14: Terminal input status
15: Terminal output status
16: Running status word
17
–20: Reserved
0
Sent PZD3
0
Sent PZD4
0
Sent PZD5
0
Sent PZD6
0
Sent PZD7
0
Sent PZD8
0
Sent PZD9
0
Sent PZD10
0
Sent PZD11
0
Sent PZD12
0
Table 9-12 Actual value of the VFD
Bit
Name
Value sent from slave to master
PZD2
FAULT CODE
Fault code, 0
–N
PZD3
SPEED FEEDBACK
Actual value of speed
PZD4
PG POS COUNTER
PG card position
PZD5
DRIVE TORQUE FEEDBACK
Actual value of torque
PZD6
Motor Running Freq.
Actual value of motor running
frequency
PZD7
DRIVE CURRENTFEEDBACK
Actual value of drive current
PZD8
DRIVE VOLTAGEFEEDBACK
Actual value of drive voltage
PZD9
Reserved
Reserved