Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-95-
Function
code
Name
Description
Setting range
Default
3: Switch between forward and
reverse rotating
4: Clear the UP/DOWN setting
5: Coast to stop
6: Switch command channels in
sequence
7: Quick commissioning mode
(based on non-factory parameter
settings)
The function code is used to select the function of the QUICK/JOG key.
0: No function
1: Jogging Press QUICK/JOG to begin the jogging running.
2: Switch displayed function codes from right to left by Press
QUICK/JOG
to shift the displayed function code from right to
left.
3: Switch between forward and reverse rotations. Press
QUICK/JOG
to shift the direction of the frequency commands.
This function is only valid in the keypad command channels.
4: Clear the UP/DOWN setting. Press QUICK/JOG to clear the set values of UP/DOWN.
5: Coast to stop. Press QUICK/JOG to coast to stop.
6: Switch command channels in sequence Press QUICK/ JOG to switch command channels in sequence.
7: Quick commissioning mode (based on non-factory parameter settings)
Note: When QUICK/JOG is used to shift between forward rotation and reverse rotation, the VFD does not record
the state after shifting during power off. The VFD will run according to the running direction set by P00.13 during
next power on.
Function
code
Name
Description
Setting range
Default
P07.03
Sequence of
switching
running-command
channels by pressing
QUICK
0:
Keypad→Terminal→Communication
1: Keypad←→Terminal
2: Keypad←→Communication
3: Terminal←→Communication
0
–3
0
When P07.02=6, set the sequence of switching running-command channels by pressing this key.
Function
code
Name
Description
Setting range
Default
P07.04
Stop function validity
of STOP/RST
0: Valid only for keypad control
1: Valid both for keypad and terminal
control
2: Valid both for keypad and
communication control
3: Valid for all control modes
0
–3
0
Used to specify the stop function validity of STOP/RST. For fault reset, STOP/RST is valid in any conditions.
Function
code
Name
Description
Setting range
Default
P07.05
Selection 1 of
parameters to be
BIT0: Running frequency (Hz on)
BIT1: Set frequency (Hz blinking)
0x0000
–0xFFFF
0x03FF