Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-62-
Function
code
Name
Description
Setting range
Default
P00.08
Reference object of B
frequency command
0: Max. output frequency
1: A frequency command
0
–1
0
The function code is used to select the reference object of B frequency command.
0: Max. output frequency: 100% of B frequency setting corresponds to Max. output frequency.
1: A frequency command: 100% of B frequency setting corresponds to Max. output frequency. If it is necessary to adjust
on basis of A frequency command, select this setting.
Function
code
Name
Description
Setting range
Default
P00.09
Combination mode of
setting source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max(A, B)
5: Min(A, B)
0
–5
0
The function code is used to set the combination mode of setting source.
0: A. The present frequency is set to A frequency command.
1: B. The present frequency is set to B frequency command.
2: A+B. The present frequency is set to A+B frequency command.
3: A-B. The present frequency is set to A-B frequency command.
4: Max(A, B). Take the larger value between A and B frequency commands as the set frequency.
5: Min(A, B). Take the smaller value between A and B frequency commands as the set frequency.
Note: The combination can be shifted by terminal functions (P05).
Function
code
Name
Description
Setting range
Default
P00.10
Frequency set
through keypad
0.00 Hz
–P00.03 (Max. output
frequency)
0.00
–P00.03
50.00Hz
When A and B frequency commands select the keypad for setting, the value of the function code is the original setting one
of the frequency data of the VFD.
Note: A frequency and B frequency cannot be set to the same frequency reference mode.
Function
code
Name
Description
Setting range
Default
P00.11
ACC time 1
0.0
–3600.0s
0.0
–3600.0
Model
depended
P00.12
DEC time 1
0.0
–3600.0s
0.0
–3600.0
Model
depended
ACC time means the time needed if the VFD speeds up from 0Hz to the max. output frequency (P00.03).
DEC time means the time needed if the VFD speeds down from the max. output frequency (P00.03) to 0Hz.
The inverter unit has four groups of ACC/DEC time, which can be selected by P05. The factory default ACC/DEC time of
the VFD is the first group.
Function
code
Name
Description
Setting range
Default
P00.13
Running direction
0: Run at the default direction.
1: Run at the opposite direction.
2: Disable reverse running
0
–2
0