Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-181-
Function
code
Name
Description
Setting
range
Default Modify
command. Range: 0x00
–0x0F
11: Voltage setting (special for
V/F separation)
(0
–1000,
in
which
1000
corresponding to 100.0% of the
motor rated voltage)
12: AO output setting 1 (-1000
–
+1000,
in
which
1000
corresponds to 100.0%)
13: AO output setting 2 (-1000
–
+1000,
in
which
1000
corresponds to 100.0%)
P15.13
Sent PZD2
0: Disable
1: Running frequency (x100, Hz)
2: Set frequency (x100, Hz)
3: Bus voltage (x10, V)
4: Output voltage (×1, V)
5: Output current (x10, A)
6: Actual output torque (x10, %)
7: Actual output power (x10, %)
8: Rotation speed of running (x1,
RPM)
9: Linear speed of running (x1,
m/s)
10: Ramp reference frequency
11: Fault code
12: AI1 input (*100, V)
13: AI2 input (*100, V)
14: AI3 input (* 100, V)
15: PULSE frequency value
(x100, kHz)
16: Terminal input status
17: Terminal output status
18: PID reference (x100, %)
19: PID feedback (x100, %)
20: Motor rated torque
0
–20
0
○
P15.14
Sent PZD3
0
–20
0
○
P15.15
Sent PZD4
0
–20
0
○
P15.16
Sent PZD5
0
–20
0
○
P15.17
Sent PZD6
0
–20
0
○
P15.18
Sent PZD7
0
–20
0
○
P15.19
Sent PZD8
0
–20
0
○
P15.20
Sent PZD9
0
–20
0
○
P15.21
Sent PZD10
0
–20
0
○
P15.22
Sent PZD11
0
–20
0
○
P15.23
Sent PZD12
0
–20
0
○
P15.24
Temporary variable 1 for
PZD sending
0
–65535
0
–65535
0
○
P15.25
DP communication timeout
time
0.0 (invalid), 0.1
–60.0s
0.0
–60.0
0.0s
○
P15.26
CAN communication timeout
time
0.0 (invalid), 0.1
–60.0s
0.0
–60.0
0.0s
○
P15.27
CANopen communication
baud rate
0: 1000k
1: 800k
2: 500k
3: 250k
4: 125k
5: 100k
6: 50k
7: 20k
0
–7
0
◎