Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-29-
Setting
Function
Description
3
External fault
After receiving the external fault signal, the PWM rectifier reports the
fault and stops. However, the main contactor is still connected and
the diode works properly.
4
Reserved
5
Enabling run
The PWM rectifier can run only after the terminal function is enabled.
6
–12
Reserved
13
Clear accumulative
electricity
consumption
When the function is enabled, the accumulative electricity
consumption (specified by P07.17 and P07.18) of the PWM rectifier
is cleared.
14
Keep accumulative
electricity
consumption
When the function is enabled, the current running of the PWM
rectifier does not affect its electricity consumption.
15
Reserved
Function
code
Name
Description
Setting range
Default
P05.12
S1 switch-on delay
The function codes specify the delay
time corresponding to the electrical
level changes when the
programmable input terminals switch
on or switch off.
0.000
–60.000
0.000s
P05.13
S1 switch-off delay
0.000s
P05.14
S2 switch-on delay
0.000s
P05.15
S2 switch-off delay
0.000s
P05.16
S3 switch-on delay
0.000s
P05.17
S3 switch-off delay
0.000s
P05.18
S4 switch-on delay
0.000s
P05.19
S4 switch-off delay
0.000s
Si Electrical
level
Si Valid
Invalid
Switch-off delay
Switch-on delay
Invalid
Valid
Function
code
Name
Description
Setting range
Default
P05.28
AI1 lower limit
0.00V
–P05.30
0.00
–P05.30
0.00V
P05.29
Corresponding
setting of AI1 lower
limit
-100.0%
–100.0%
-100.0
–100.0
0.0%
P05.30
AI1 upper limit
P05.28
–10.00V
P05.28
–10.00
10.00V
P05.31
Corresponding
setting of AI1 upper
limit
-100.0%
–100.0%
-100.0
–100.0
100.0%
P05.32
AI1 input filter time 0.000s
–10.000s
0.000
–10.000
0.100s
P05.33
AI2 lower limit
-10.00V
–P05.35
-10.00
–P05.35
0.00V
P05.34
Corresponding
setting of AI2 lower
limit
-100.0%
–100.0%
-100.0
–100.0
0.0%
P05.35
AI2 middle value
P05.33
–P05.37
P05.33
–P05.37
0.00V