Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-30-
Function
code
Name
Description
Setting range
Default
P05.36
Corresponding
setting of AI2 middle
value
-100.0%
–100.0%
-100.0
–100.0
0.0%
P05.37
AI2 upper limit
P05.35
–10.00V
P05.35
–10.00
10.00V
P05.38
Corresponding
setting of AI2 upper
limit
-100.0%
–100.0%
-100.0
–100.0
100.0%
P05.39
AI2 input filter time 0.000s
–10.000s
0.000
–10.000
0.100s
P05.40
AI3 lower limit
0.00V
–P05.42
0.00
–P05.42
0.00V
P05.41
Corresponding
setting of AI3 lower
limit
-100.0%
–100.0%
-100.0
–100.0
0.0%
P05.42
AI3 upper limit
P05.40
–10.00V
P05.40
–10.00
10.00V
P05.43
Corresponding
setting of AI3 upper
limit
-100.0%
–100.0%
-100.0
–100.0
100.0%
P05.44
AI3 input filter time 0.000s
–10.000s
0.000
–10.000
0.100s
The function code is used to define the relationship between the analog input voltage and its corresponding setting. When
the analog input voltage exceeds the range from the upper limit to the lower limit, the upper limit or lower limit is used.
When the analog input is current input, 0mA
–20mA current corresponds to 0V–10V voltage.
In different applications, 100.0% of the analog setting corresponds to different nominal values. See the descriptions of
each application section for details.
The following figure illustrates the cases of several settings:
-100%
100%
Corresponding
setting
AI
-10V
10V
20mA
0
AI2
AI1, AI3
Input filter time: to adjust the sensitivity of analog input. Increasing the value properly can enhance analog input
anti-interference but may reduce the sensitivity of analog input.
Note: AI1 and AI3 support the 0
–10V/0–20mA input. When AI1 and AI3 select the 0–20mA input, the
corresponding voltage of 20mA is 10V. AI2 supports the -10V
–+10V input.
P06 group
—Output terminals
Function
code
Name
Description
Setting range
Default
P06.00
Digital output terminal
polarity
0x0
–0xF
0x0
–0xF
0x0
The function code is used to select output terminal polarity.
When a bit is 0, the output terminal is positive; when a bit is 1, the output terminal is negative.