Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-49-
Function
code
Name
Description
Setting
range
Default Modify
P03.26
Overmodulation
proportional coefficient P
0.001
–60.000
0.001
–
60.000
5.000
○
P03.27
Overmodulation integral
coefficient I
0.01
–30.000
0.01
–
30.000
5.00
○
P03.28
Phase-lock loop integral 0
–10
0
–10
10%
○
P03.29
–
P03.30
Reserved
●
P05 group
––Input terminals
P05.00
Reserved
P05.01
Digital input terminal
polarity
0x0
–0xF
0 indicates positive.
BIT0: S1
BIT1: S2
BIT2: S3
BIT3: S4
0x0
–0xF
0x0
◎
P05.02
Reserved
●
P05.03
Digital input filter time
0.000
–1.000s
0.000
–
1.000
0.000s
○
P05.04
Function of S1 terminal 0: No function
1: Run
2: Reset faults
3: External fault
4: Reserved
5: Enable
6: Reserved
7
–12: Reserved
13: Clear accumulative electricity
consumption
14: Keep accumulative electricity
consumption
15: Reserved
0
–15
1
◎
P05.05
Function of S2 terminal
2
◎
P05.06
Function of S3 terminal
0
◎
P05.07
Function of S4 terminal
0
◎
P05.08
–
P05.11
Reserved
0
●
P05.12
S1 switch-on delay
0.000
–60.000s
0.000
–
60.000
0.000s
○
P05.13
S1 switch-off delay
0.000
–60.000s
0.000
–
60.000
0.000s
○
P05.14
S2 switch-on delay
0.000
–60.000s
0.000
–
60.000
0.000s
○
P05.15
S2 switch-off delay
0.000
–60.000s
0.000
–
60.000
0.000s
○
P05.16
S3 switch-on delay
0.000
–60.000s
0.000
–
60.000
0.000s
○
P05.17
S3 switch-off delay
0.000
–60.000s
0.000
–
60.000
0.000s
○
P05.18
S4 switch-on delay
0.000
–60.000s
0.000
–
60.000
0.000s
○
P05.19
S4 switch-off delay
0.000
–60.000s
0.000
–
60.000
0.000s
○