Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-87-
Sin Three-wire control; FWD: Forward running; REV: Reverse running
Note: For two-wire controlled running mode, when the FWD/REV terminal is valid, if the VFD stops due to a stop
command given by another source, the VFD does not run again after the stop command disappears even if the
control terminal FWD/REV is still valid. To make the VFD run, you need to trigger FWD/REV again, for example,
PLC single-cycle stop, fixed-length stop, and valid STOP/RST stop during terminal control. (See P07.04.)
Function
code
Name
Description
Setting range
Default
P05.14
S1 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.15
S1 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.16
S2 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.17
S2 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.18
S3 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.19
S3 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.20
S4 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.21
S4 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.22
S5 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.23
S5 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.24
S6 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.25
S6 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.26
S7 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.27
S7 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.28
S8 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.29
S8 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.30
HDI switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P05.31
HDI switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
Used to specify the delay time corresponding to the electrical level changes when the programmable input terminals
switch on or switch off.
Si electrical level
Si valid
invalid
invalid
Switch-on
delay
Switch-off
delay
valid
Function
code
Name
Description
Setting range
Default
P05.32
AI1 lower limit
0.00V
–P05.34
0.00
–P05.34
0.00V
P05.33
Corresponding setting of
AI1 lower limit
-100.0%
–100.0%
-100.0
–100.0
0.0%
P05.34
AI1 upper limit
P05.32
–10.00V
P05.32
–10.00
10.00V
P05.35
Corresponding setting of
AI1 upper limit
-100.0%
–100.0%
-100.0
–100.0
100.0%
P05.36
AI1 input filter time
0.000s
–10.000s
0.000
–10.000
0.100s
P05.37
AI2 lower limit
-10.00V
–P05.39
-10.00V
–P05.39
0.00V
P05.38
Corresponding setting of
AI2 lower limit
-100.0%
–100.0%
-100.0
–100.0
0.0%
P05.39
AI2 middle value
P05.37
–P05.41
P05.37
–P05.41
0.00V
P05.40
Corresponding setting of
AI2 middle value
-100.0%
–100.0%
-100.0
–100.0
0.0%
P05.41
AI2 upper limit
P05.39
–10.00V
P05.39
–10.00
10.00V