Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-157-
Function
code
Name
Description
Setting
range
Default Modify
27: Reserved
28: Reserved
29: Disable torque control
30: Disable ACC/DEC
31: Reserved
32: Reserved
33: Clear the frequency
increase/decrease setting
temporarily
34: DC braking for stop
35: Switch from motor 1 to motor
2
36: Switch the running command
channel to keypad
37: Switch the running command
channel to terminal
38: Switch the running command
channel to communication
39: Pre-exciting command
40: Clear electricity consumption
41: Keep electricity consumption
42: External fault input 2
43: Enable switching to power
frequency run
44: Switch to the master
45: Switch to the slave
46: Switch-on signal feedback of
rectifier
47
–63: Reserved
P05.10
Input terminal polarity
0x000
–0x1FF
0x000
–
0x1FF
0x000
○
P05.11
Digital input filter time
0.000
–1.000s
0.000
–1.000 0.010s
○
P05.12
Virtual terminal setting
0: Virtual input terminals are
invalid
1: MODBUS communication
virtual terminals are valid
2: PROFIBUS/CANopen
communication virtual terminals
are valid
3: Ethernet virtual terminals are
valid
4: Reserved
0
–4
0
◎
P05.13
Terminal control mode
0: Two-wire control mode 1
1: Two-wire control mode 2
2: Three-wire control mode 1
3: Three-wire control mode 2
0
–3
0
◎
P05.14
S1 switch-on delay
0.000
–50.000s
0.000
–
50.000
0.000s
○