Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-179-
Function
code
Name
Description
Setting
range
Default Modify
P13.17
SM brake component
enabling threshold voltage
200.0
–6000.0V
200.0
–
6000.0
Model
depended
○
P13.18
SM brake component
enabling time setting
0.000
–4.000s
0.000
–4.000 1.000s
○
P13.19
–
P13.20
Reserved
P13.21
Start frequency of
mal-adjustment fault
determination
0.00
–50.00Hz
0.00
–50.00 5.00Hz
P13.22
Mal-adjustment fault
detection deviation angle
0.00
–359.99°
0.00
–359.99 36.00°
P13.23
Enabling protection against
runaway fault
0: Invalid
1: Valid
0
–1
0
P13.24
–
P13.25
Reserved
P14 group
––Serial communication
P14.00
Local communication
address
1
–247; 0 indicates a broadcast
address
1
–247
1
○
P14.01
Communication baud rate
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
0
–6
4
○
P14.02
Data bit check
0: No check (N, 8, 1) for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check (O, 8, 2) for RTU
0
–5
1
○
P14.03
Communication response
delay
0
–200ms
0
–200
5ms
○
P14.04 Communication timeout time 0.0 (invalid); 0.1
–60.0s
0.0
–60.0
0.0s
○
P14.05
Transmission error
processing
0: Report an alarm and coast to
stop
1: Keep running without reporting
an alarm
2: Stop in enabled stop mode
without
reporting
an
alarm
(applicable
only
to
communication mode)
3: Stop in enabled stop mode
without
reporting
an
alarm
(applicable to any mode)
0
–3
0
○
P14.06
Communication processing
action
0x00
–0x11
Ones place: Action upon the
0x00
–0x11
0x00
○