Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-178-
Function
code
Name
Description
Setting
range
Default Modify
P12.26
Overload protection of motor
2
0: No protection
1: Common motor (with
low-speed compensation)
2: Frequency-variable motor
(without low-speed
compensation)
0
–2
2
◎
P12.27
Overload protection
coefficient of motor 2
20.0%
–120.0%
20.0
–120.0 100.0%
○
P12.28
Power calibration coefficient
of motor 2
0.00
–3.00
0.00
–3.00
1.00
○
P12.29 Parameter display of motor 2
0: Display based on motor type
1: Display all
0
–1
0
○
P13 group
––SM control
P13.00
Reduction coefficient of
pull-in current
0.0
–100.0%
0.0
–100.0
80.0%
○
P13.01 Detection mode of initial pole
0: Not detect
1: High frequency
superimposition (reserved)
2: Pulse superimposition
(reserved)
0
–3
0
◎
P13.02
Pull-in current 1
0.0%
–100.0% (of the motor rated
current)
0.0
–100.0
20.0%
○
P13.03
Pull-in current 2
0.0%
–100.0% (of the motor rated
current)
0.0
–100.0
10.0%
○
P13.04
Switch-over frequency of
pull-in current
0.00Hz
–P00.03 (Max. output
frequency)
0.00
–P00.03 10.00Hz
○
P13.05
High frequency
superimposed frequency
200Hz
–1000Hz
200
–1000
500Hz
◎
P13.06
High frequency
superimposed voltage
0.0
–300.0% (of the motor rated
voltage)
0.0
–300.0
50.0%
◎
P13.07
Frequency drop rate during
current limit
0
–400.0
0
–400.0
0
○
P13.08
BUG control word
0
–65535
0
–65535
0
○
P13.09
Frequency switchover point 0
–655.35
0
–655.35
2.00
○
P13.10
Angle compensation
0
–6553.5
0
–6553.5
0
○
P13.11
Maladjustment detection
time
0.0
–10.0s
0.0
–10.0
0.5s
○
P13.12
High frequency
compensation coefficient
0
–100.0%
0
–100.0
0.0%
○
P13.13
Short-circuit braking current 0.0
–150.0% (relative to the VFD) 0.0–150.0
0.0%
○
P13.14
Hold time of short-circuit
braking for start
0.00
–50.00s
0.00
–50.00
0.00s
○
P13.15
Hold time of short-circuit
braking for stop
0.00
–50.00s
0.00
–50.00
0.00s
○
P13.16
SM brake component
enabling
0
–1
0
–1
0
○