Goodrive3000 series medium voltage VFD
Goodrive3000 rectifier
-42-
Value
Name
Description
feedback
9
Reactive current
feedback
100% corresponds to the rectifier rated current.
10
Fault code
11
AI1 input
*100, V
12
AI2 input
*100, V
13
AI3 input
*100, V
14
Terminal input
status
15
Terminal output
status
16
Running status word
17
–20
Reserved
P12.13
–P12.23 can be modified in any state.
Function
code
Name
Description
Setting range
Default
P12.24
Temporary variable 1
for PZD sending
0
–65535
0
–65535
0
The function code is used as a temporary variable for PZD sending.
P12.24 can be written in any state.
Function
code
Name
Description
Setting range
Default
P12.25
DP communication
timeout time
0.0 (invalid), 0.1
–60.0s
0.0
–60.0
0.0s
When the function code is set to 0.0s, DP communication timeout is not considered as a fault. When it is set to a non-zero
value, the rectifier reports a DP communication fault (E-DP) if the communication interval exceeds the value.
P13 group
––Ethernet communication
Function
code
Name
Description
Setting range
Default
P13.00
Ethernet
communication rate
0: Self adaptive
1: 100M full duplex
2: 100M half duplex
3: 10M full duplex
4: 10M half duplex
0
–4
0
The function code is used to set the Ethernet communication rate. Generally, the default value is retained.
Function
code
Name
Description
Setting range
Default
P13.01
IP address 1
0
–255
0
–255
192
P13.02
IP address 2
0
–255
0
–255
168
P13.03
IP address 3
0
–255
0
–255
0
P13.04
IP address 4
0
–255
0
–255
1
P13.05
Subnet mask 1
0
–255
0
–255
255
P13.06
Subnet mask 2
0
–255
0
–255
255
P13.07
Subnet mask 3
0
–255
0
–255
255
P13.08
Subnet mask 4
0
–255
0
–255
0