Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-154-
Function
code
Name
Description
Setting
range
Default Modify
P04.02
Torque boost cut-off of
motor 1
0.0%
–50.0% (of the rated
frequency of motor 1)
0.0
–50.0
20.0%
○
P04.03
V/F frequency point 1 of
motor 1
0.00Hz
–P04.05
0.00
–P04.05 0.00Hz
○
P04.04
V/F voltage point 1 of motor
1
0.0%
–110.0% (of the rated
voltage of motor 1)
0.0
–110.0
0.0%
○
P04.05
V/F frequency point 2 of
motor 1
P04.03
–P04.07
P04.03
–
P04.07
0.00Hz
○
P04.06
V/F voltage point 2 of motor
1
0.0%
–110.0% (of the rated
voltage of motor 1)
0.0
–110.0
0.0%
○
P04.07
V/F frequency point 3 of
motor 1
P04.05
–P02.02
(Rated
frequency of motor 1)
or
P04.05
–P02.16
(Rated
frequency of motor 1)
P04.05
–
Rated
frequency of
motor 1
0.00Hz
○
P04.08
V/F voltage point 3 of motor
1
0.0%
–110.0% (of the rated
voltage of motor 1)
0.0
–110.0
0.0%
○
P04.09
V/F slip compensation gain
of motor 1
0.0
–200.0%
0.0
–200.0
100.0%
○
P04.10
Low-frequency oscillation
control factor of motor 1
0
–100
0
–100
10
○
P04.11
High-frequency oscillation
control factor of motor 1
0
–100
0
–100
10
○
P04.12
Oscillation control threshold
of motor 1
0.00Hz
–P00.03 (Max. output
frequency)
0.00
–P00.03 30.00 Hz
○
P04.13
V/F curve setting of motor 2
0: Straight-line V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve
(power of 1.3)
3: Torque-down V/F curve
(power of 1.7)
4: Torque-down V/F curve
(power of 2.0)
5: Customized V/F curve (V/F
separation)
0
–5
0
◎
P04.14
Torque boost of motor 2
0.0%: (automatic)
0.1%
–10.0%
0.0
–10.0
0.0%
○
P04.15
Torque boost cut-off of
motor 2
0.0%
–50.0% (of the rated
frequency of motor 2)
0.0
–50.0
20.0%
○
P04.16
V/F frequency point 1 of
motor 2
0.00Hz
–P04.18
0.00
–P04.18 0.00Hz
○
P04.17
V/F voltage point 1 of motor
2
0.0%
–110.0% (of the rated
voltage of motor 2)
0.0
–110.0
0.0%
○
P04.18
V/F frequency point 2 of
motor 2
P04.16
–P04.20
P04.16
–
P04.20
0.00Hz
○
P04.19
V/F voltage point 2 of motor
2
0.0%
–110.0% (of the rated
voltage of motor 2)
0.0
–110.0
0.0%
○