Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-117-
Functio
n code
Name
Description
Setting
range
Default
Hundreds place:
0: Detect all the time.
1: Detect during constant speed running.
P11.09
Overload pre-alarm
detection threshold
P11.11
–200%
P11.11
–200 150%
P11.10
Overload pre-alarm
detection time
0.1
–60.0s
0.1
–60.0
1.0s
P11.11
Underload pre-alarm
detection threshold
0%
– P11.09
0
–P11.09
50%
P11.12
Underload pre-alarm
detection time
0.1
–60.0s
0.1
–60.0
1.0s
If the VFD or motor output current is larger than the overload pre-alarm detection level (P11.09), and the duration exceeds
the overload pre-alarm detection time (P11.10), overload pre-alarm signal will be outputted.
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time t
Pre-alarm time t
Underload pre-alarm signal will be outputted if the output current of the VFD or motor is lower than underload pre-alarm
detection level (P11.11), and the duration exceeds underload pre-alarm detection time (P11.12).
Note:
The underload pre-alarm detection threshold (P11.11) should be smaller than the overload pre-alarm detection
threshold (P11.09).
Function
code
Name
Description
Setting range
Default
P11.13
Fault output terminal
action upon fault
occurring
0x00
–0x11
Ones place:
0: Act upon an undervoltage fault
1: Do not act upon an undervoltage
fault
Tens place:
0: Act during automatic reset
1: Do not act during the automatic
reset period
0x00
–0x11
0x00
Function
code
Name
Description
Setting
range
Default
P11.14
Speed deviation
detection value
0.0
–50.0%
0.0
–50.0
10.0%