Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-74-
2.
The options 4, 5, 8, and 9 are available only when corresponding expansion cards are configured.
Function
code
Name
Description
Setting range
Default
P03.12
Torque set through
keypad
-300.0%
–300.0% (of the motor rated
current)
-300.0
–300.0
50.0%
When P03.11=1, the torque is set on the keypad.
Function
code
Name
Description
Setting range
Default
P03.13
Torque reference
filter time
0.000
–10.000s
0.000
–10.000
0.100s
The function code is used to set the torque reference filter time.
Function
code
Name
Description
Setting
range
Default
P03.14
Setting source of
forward rotation
upper-limit frequency
in torque control
0: Keypad (Set P03.16 for P03.14, and
set P03.17 for P03.15)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDI
5: Multi-step setting
6: MODBUS communication
7: PROFIBUS/CANopen communication
8: Ethernet communication
9: Reserved
0
–9
0
P03.15
Setting source of
reverse rotation
upper-limit frequency
in torque control
0
–9
0
Note: For setting methods 1
–9, 100% corresponds to the maximum frequency. The options 3, 4, 7, and 8 are
available only when corresponding expansion cards are configured.
Function
code
Name
Description
Setting
range
Default
P03.16
Forward rotation
upper-limit frequency set
through keypad in torque
control
0.00Hz
–P00.03
0.00
–P00.03 20.00Hz
P03.17
Reverse rotation
upper-limit frequency set
through keypad in torque
control
0.00Hz
–P00.03
0.00
–P00.03 20.00Hz
The function code is used to set the frequency upper limits. 100% corresponds to the max. frequency. P03.16 sets the
value for P03.14, and P03.17 sets the value for P03.15.
Function
code
Name
Description
Setting
range
Default
P03.18
Setting source of
electromotive torque
upper limit
0: Keypad (Set P03.20 for P03.18, and
set P03.21 for P03.19)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDI
5: MODBUS communication
0
–8
0
P03.19
Setting source of
braking torque upper
limit
0
–8
0