Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-69-
Output frequency
Running
Power off
Power on
Running
t
t1
t2
t1=P01.22
t2=P01.23
Function
code
Name
Description
Setting range
Default
P01.23
Start delay
0.0
–60.0s
0.0
–60.0
0.0s
After a VFD running command is given, the VFD is in standby state and restarts with the delay defined by P01.23 to
implement brake release.
Function
code
Name
Description
Setting range
Default
P01.24
Stop speed delay
0.0
–100.0s
0.0
–100.0
0.0s
The function code is used to set the delay time of stop speed of the VFD. When the actual output frequency of the VFD is
equal to P01.15 and it lasts over the time set by P01.24, the VFD will stop.
T
Output frequency
Stop
speed
P01.24
running
Function
code
Name
Description
Setting range
Default
P01.25
0Hz output selection
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current
for stop
0
–2
0
The function code is used to select the output type of the VFD at 0Hz.
P02 group
––Parameters of motor 1
Function
code
Name
Description
Setting range
Default
P02.00
Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
–1
0
The function code is used to select the type of motor 1.
Function
code
Name
Description
Setting range
Default
P02.01
Rated power of AM 1 0.1
–3000.0kW
0.1
–3000.0
Model
depended
P02.02
Rated frequency of
AM 1
0.01Hz
–P00.03 (Max. output
frequency)
0.01
–P00.03
50.00Hz
P02.03
Rated speed of AM 1 1
–36000rpm
1
–36000
Model
depended