Goodrive3000 series medium voltage VFD
PROFIBUS communication
-225-
LED No.
Name
Color
Function
The length of the user parameter data set during the module
initialization is different from that during the network configuration.
It blinks at the frequency of 2 Hz when user parameter data is
incorrect: The length or content of the user parameter data set during
the module initialization is different from that during the network
configuration.
It blinks at the frequency of 4 Hz when an error occurs in the ASIC
initialization of communication.
9.6 Related function codes
Related function codes for rectifier unit
Function
code
Name
Description
Setting
range
Default
P12.00
Module type
0: PROFIBUS
0
0
P12.01
Module address
0
–127
0
–127
2
P12.02
Received PZD2
0: Disable
1: DC voltage setting (0
–40000; Unit: 0.1V)
2
–4: Reserved
5: AO setting 1
(-1000
–1000, 1000 corresponding to 100.0%)
6: AO setting 2
(-1000
–1000, 1000 corresponding to 100.0%)
7
–13: Reserved
0
–13
0
P12.03
Received PZD3
0
–13
0
P12.04
Received PZD4
0
–13
0
P12.05
Received PZD5
0
–13
0
P12.06
Received PZD6
0
–13
0
P12.07
Received PZD7
0
–13
0
P12.08
Received PZD8
0
–13
0
P12.09
Received PZD9
0
–13
0
P12.10
Received PZD10
0
–13
0
P12.11
Received PZD11
0
–13
0
P12.12
Received PZD12
0
–13
0
P12.13
Sent PZD2
0: Disable
1: DC voltage (* 10, V)
2: DC voltage feedback (* 10, V)
3: Input voltage valid value (* 10, V)
4: Input current valid value (* 10, A)
5: Input power (* 10, kW)
6: Input power factor (*100)
7: Grid frequency (* 10, Hz)
8: Active current feedback (100% corresponds to
the rectifier rated current.)
9: Reactive current feedback (100% corresponds
to the rectifier rated current.)
10: Fault code
11: AI1 input (*100, V)
12: AI2 input (*100, V)
13: AI3 input (* 100, V)
14: Terminal input status
15: Terminal output status
16: Running status word
17
–20: Reserved
0
–20
0
P12.14
Sent PZD3
0
–20
0
P12.15
Sent PZD4
0
–20
0
P12.16
Sent PZD5
0
–20
0
P12.17
Sent PZD6
0
–20
0
P12.18
Sent PZD7
0
–20
0
P12.19
Sent PZD8
0
–20
0
P12.20
Sent PZD9
0
–20
0
P12.21
Sent PZD10
0
–20
0
P12.22
Sent PZD11
0
–20
0
P12.23
Sent PZD12
0
–20
0
P12.24
Temporary variable 1
for PZD sending
0
–65535
0
–65535
0