Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-184-
Function
code
Name
Description
Setting
range
Default Modify
P18.06
Motor temperature display -200.0
–200.0
-200.0
–
200.0
●
P18.07
Frequency reference sent by
master
-100.00
–100.0% (of the max.
VFD frequency)
-100.00
–
100.0
●
P18.08
Speed loop output sent by
master
-300.00
–300.0% (of the motor
rated current)
-300.00
–
300.00
●
P18.09
Frequency reference
command received by slave
-100.00
–100.0% (of the max.
VFD frequency)
-100.00
–
100.0
●
P18.10
Torque command received
by slave
-300.00
–300.0% (of the motor
rated current)
-300.00
–
300.00
●
P18.11
Voltage of upper half bus 0
–65535
0
–65535
●
P18.12
Voltage of lower half bus
0
–65535
0
–65535
●
P18.13
Software version (FPAG) 1.00
–655.35
●
P18.14
Reserved/Max. midpoint
voltage balance
compensation
Reserved/0
–512
Reserved/
0
–512
Reserved
/400
●
P18.15
Reserved/Midpoint voltage
balance mode
Reserved/
0: bang-bang control
1: P control
2: PI control
Reserved/
0
–2
Reserved
/1
●
P18.16
Max. midpoint voltage
balance
compensation/Midpoint
voltage balance algorithm
Kp
0
–512/0–500
0
–512/ 0–
500
100/200
●
P18.17
Midpoint voltage balance
mode/Midpoint voltage
balance algorithm Ki
0: bang-bang control
1: P control
2: PI control
/0
–10
0
–2/0–10
0/6
●
P18.18
Midpoint voltage balance
algorithm Kp/Grid voltage
and main contactor condition
selection
0
–5000/
0: Grid voltage calculation
1: P20.14
0
–5000/0–1
400/0
●
P18.19
Midpoint voltage balance
algorithm Ki/Input grid
voltage balance degree
0
–10/0–65535
0
–10/0–
65535
6/0
●
P18.20
Max. bus voltage recorded
by the system
0.0
–6550.0V
0.0
–6550.0
0.0V
●
P18.21
Max. upper bus voltage
recorded by the system
0.0
–3275.0V
0.0
–3275.0
0.0V
●
P18.22
Max. lower bus voltage
recorded by the system
0.0
–3275.0V
0.0
–3275.0
0.0V
●
P18.23 Sum of three phase currents 0
–65535
0
–65535
0
●
P18.24
Speed display selection in
vector control
0: Identification speed
1: Ramp reference
0
–1
0
◎
P19 group
––External temperature detection
P19.00 Motor temperature detection
0: Invalid
1: PT100
0
–4
0
○