Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-64-
3: Static autotuning 2
Only the first 3 parameters are autotuned. It is applicable in scenarios where the motor cannot be disconnected from
load.
Note:
1.
Rotary autotuning is recommended.
2.
For 4-quadrant VFDs, it is recommended not to run the rectifier during parameter autotuning, otherwise the accuracy
is affected.
3.
The power difference between the motor and the VFD should be in 2 grades during parameter autotuning, otherwise
affect the accuracy.
Function
code
Name
Description
Setting range
Default
P00.16
AVR function
selection
0: Invalid
1: Valid during the whole procedure
0
–1
1
The function code is used to enable the AVR function.
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the VFD can eliminate the impact on the output voltage of the VFD because of the bus
voltage fluctuation.
Function
code
Name
Description
Setting range
Default
P00.18
Function parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
0
–2
0
Note:
1.
After the selected operation is performed, the function code is automatically restored to 0.
2.
Restoring the default values may delete the user password. Exercise caution when using this function.
P01 group
––Start and stop control
Function
code
Name
Description
Setting range
Default
P01.00
Start mode
0: Direct start
1: Start after DC braking
2: Start after rotating speed tracking
0
–2
0
0: Direct start. Start from the starting frequency P01.01.
1: Start after DC braking. Start the motor from the starting frequency after DC braking (Set the parameters P01.03 and
P01.04). It is suitable in cases where reverse rotation may occur to the small inertia load during starting.
2. Start after rotating speed tracking. The VFD automatically tracks the rotating speed and direction of the motor, and start
the rotating motor smoothly. It is suitable in cases where reverse rotation may occur to the large inertia load during
starting.
Function
code
Name
Description
Setting range
Default
P01.01
Starting frequency of
direct start
0.00
–50.00Hz
0.00
–50.00
0.50Hz
The function code indicates the initial frequency during VFD start. See P01.02 (Starting frequency hold time) for detailed
information.