Goodrive3000 series medium voltage VFD
Goodrive3000 inverter
-91-
Setting
Function
Description
the value is 0, the OFF signal is output.
26
DC bus voltage
established
Output is valid when the bus voltage exceeds the undervoltage
threshold.
27
–28
Reserved
29
Motor OH pre-alarm
The signal is valid when the temperature of the motor is larger than
the set pre-alarm temperature and less than motor overheat
protection point.
30
Phase-locked and
synchronous output at
power frequency
When this terminal is valid and P22.00 is set to 1, the running
command performs the switchover from variable frequency to
power frequency.
Function
code
Name
Description
Setting range
Default
P06.06
Output terminal
polarity selection
0x00
–0x1F
0x00
–0x1F
0x00
The function code is used to set the polarity of output terminals.
When a bit is 0, the output terminal is positive; when a bit is 1, the output terminal is negative.
BIT5
BIT4
BIT3
BIT2
BIT1
BIT0
Reserved
RO3
RO2
RO1
Y1
HDO
Functio
n code
Name
Description
Setting range
Default
P06.07
Y switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P06.08
Y switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P06.09
HDO switch-on delay
0.000
–50.000s (valid when P06.00 is 1) 0.000–50.000
0.000s
P06.10
HDO switch-off delay
0.000
–50.000s (valid when P06.00 is 1) 0.000–50.000
0.000s
P06.11
RO1 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P06.12
RO1 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P06.13
RO2 switch-on delay
0.000
–50.000s
0.000
–50.000
0.000s
P06.14
RO2 switch-off delay
0.000
–50.000s
0.000
–50.000
0.000s
P06.15
RO3 switch-on delay
0.000
–50.000s
0.00
–50.00
0.000s
P06.16
RO3 switch-off delay
0.000
–50.000s
0.00
–50.00
0.000s
The function codes specify the delay time corresponding to the electrical level changes when the programmable output
terminals switch on or switch off.
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Function
code
Name
Description
Setting range Default
P06.17
AO1 output
0: Running frequency
1: Set frequency
2: Ramp reference frequency
3: Rotational speed
4: Output current (relative to the VFD)
0
–30
0
P06.18
AO2 output
0
–30
0
0
–30
0
P06.19
AO3 output
P06.20
HDO high-speed