7-52
PQM Power Quality Meter
GE Power Management
7.3 MODBUS MEMORY MAP
7 MODBUS COMMUNICATIONS
7
FLASH
MESSAGE
continued
121D
Flash message characters 27 and 28
32 to 127
1
ASCII
F10
""
121E
Flash message characters 29 and 30
32 to 127
1
ASCII
F10
""
121F
Flash message characters 31 and 32
32 to 127
1
ASCII
F10
""
1220
Flash message characters 33 and 34
32 to 127
1
ASCII
F10
""
1221
Flash message characters 35 and 36
32 to 127
1
ASCII
F10
""
1222
Flash message characters 37 and 38
32 to 127
1
ASCII
F10
""
1223
Flash message characters 39 and 40
32 to 127
1
ASCII
F10
""
1224
Reserved
to
↓
↓
↓
↓
↓
↓
125F
Reserved
DATA
LOGGER
1260
Log 1 Interval (high)
1 to 86400
1
s
F3
3600
1261
Log 1 Interval (low)
1 to 86400
1
s
F3
3600
1262
Log 2 Interval (high)
1 to 86400
1
s
F3
3600
1263
Log 2 Interval (low)
1 to 86400
1
s
F3
3600
1264
Log 1 Mode
0 to 1
1
---
F32
0 = RUN TO FILL
1265
Log 2 Mode
0 to 1
1
---
F32
0 = RUN TO FILL
1266
Log Size Determination
0 to 1
1
---
F33
0 = AUTOMATIC
1267
Log 1 Size
0 to 100
1
%
F1
0%
1268
Data Log Memory Access Block Number
0 to 511
1
---
F1
0
1269
Stop Data Log 1
0 to 1
1
---
F31
0=NO
126A
Stop Data Log 2
0 to 1
1
---
F31
0=NO
126B
Reserved
to
↓
↓
↓
↓
↓
↓
126F
Reserved
1270
Ia Log Assignment
0 to 3
1
---
F34
0 = NONE
1271
Ib Log Assignment
0 to 3
1
---
F34
0 = NONE
1272
Ic Log Assignment
0 to 3
1
---
F34
0 = NONE
1273
Iavg Log Assignment
0 to 3
1
---
F34
0 = NONE
1274
In Log Assignment
0 to 3
1
---
F34
0 = NONE
1275
I Unbalance Log Assignment
0 to 3
1
---
F34
0 = NONE
1276
Van Log Assignment
0 to 3
1
---
F34
0 = NONE
1277
Vbn Log Assignment
0 to 3
1
---
F34
0 = NONE
1278
Vcn Log Assignment
0 to 3
1
---
F34
0 = NONE
1279
Vpavg Log Assignment
0 to 3
1
---
F34
0 = NONE
127A
Vab Log Assignment
0 to 3
1
---
F34
0 = NONE
127B
Vbc Log Assignment
0 to 3
1
---
F34
0 = NONE
127C
Vca Log Assignment
0 to 3
1
---
F34
0 = NONE
127D
Vlavg Log Assignment
0 to 3
1
---
F34
0 = NONE
127E
V Unbalance Log Assignment
0 to 3
1
---
F34
0 = NONE
127F
Pa Log Assignment
0 to 3
1
---
F34
0 = NONE
1280
Qa Log Assignment
0 to 3
1
---
F34
0 = NONE
1281
Sa Log Assignment
0 to 3
1
---
F34
0 = NONE
1282
PFa Log Assignment
0 to 3
1
---
F34
0 = NONE
1283
Pb Log Assignment
0 to 3
1
---
F34
0 = NONE
Table 7–10: PQM MEMORY MAP (Sheet 38 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...