7-60
PQM Power Quality Meter
GE Power Management
7.3 MODBUS MEMORY MAP
7 MODBUS COMMUNICATIONS
7
F102
LED STATUS FLAGS:
(0 = INACTIVE, 1 = ACTIVE)
FFFF
AUX 1 Relay
0001
AUX 2 Relay
0002
AUX 3 Relay
0004
ALARM
0008
PROGRAM
0010
SIMULATION
0020
ALARM Relay
0040
SELF TEST
0080
Not Used
0100
Not Used
0200
Not Used
0400
Not Used
0800
Not Used
1000
Not Used
2000
Not Used
4000
Not Used
8000
F103
LED ATTRIBUTE FLAGS
(0 = FLASHING, 1 = SOLID; ACTIVE)
FFFF
AUX 1 Relay
0001
AUX 2 Relay
0002
AUX 3 Relay
0004
ALARM
0008
PROGRAM
0010
SIMULATION
0020
ALARM Relay
0040
SELF TEST
0080
Not Used
0100
Not Used
0200
Not Used
0400
Not Used
0800
Not Used
1000
Not Used
2000
Not Used
4000
Not Used
8000
F104
OUTPUT RELAY FLAG
(0=DE-ENERGIZED,1=ENERGIZED)
FFFF
Alarm Relay
0001
Auxiliary Relay 1
0002
Auxiliary Relay 2
0004
Auxiliary Relay 3
0008
Not Used
0010
Not Used
0020
Not Used
0040
Not Used
0080
Not Used
0100
Not Used
0200
Table 7–11: MEMORY MAP DATA FORMATS (Sheet 11 of 16)
CODE
DESCRIPTION
BITMASK
F104
con’t
Not Used
0400
Not Used
0800
Not Used
1000
Not Used
2000
Not Used
4000
Not Used
8000
F105
ALARM STATUS FLAGS 1:
FFFF
Phase Undercurrent Alarm
0001
Phase Overcurrent Alarm
0002
Neutral Overcurrent Alarm
0004
Undervoltage Alarm
0008
Overvoltage Alarm
0010
Current Unbalance Alarm
0020
Voltage Unbalance Alarm
0040
Voltage Phase Reversal
0080
Power Factor Lead Alarm 1
0100
Power Factor Lead Alarm 2
0200
Power Factor Lag Alarm 1
0400
Power Factor Lag Alarm 2
0800
Positive Real Power Alarm
1000
Negative Real Power Alarm
2000
Positive Reactive Power Alarm
4000
Negative Reactive Power Alarm
8000
F106
ALARM STATUS FLAGS 2:
FFFF
Underfrequency Alarm
0001
Overfrequency Alarm
0002
Positive Real Power Demand alarm
0004
Positive Reactive Power Demand Alarm
0008
Apparent Power Demand Alarm
0010
Phase A Current Demand Alarm
0020
Phase B Current Demand Alarm
0040
Phase C Current Demand Alarm
0080
Neutral Current Demand Alarm
0100
Switch A Alarm
0200
Switch B Alarm
0400
Switch C Alarm
0800
Switch D Alarm
1000
Internal Fault Alarm
2000
Serial COM1 Failure Alarm
4000
Serial COM2 Failure Alarm
8000
F107
ALARM STATUS FLAGS 3:
FFFF
Clock Not Set Alarm
0001
Parameters Not Set Alarm
0002
Pulse Input 1 Alarm
0004
Current THD Alarm
0008
Voltage THD Alarm
0010
Analog Input Main Alarm
0020
Table 7–11: MEMORY MAP DATA FORMATS (Sheet 12 of 16)
CODE
DESCRIPTION
BITMASK
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...