1-12
PQM Power Quality Meter
GE Power Management
1.3 SPECIFICATIONS
1 OVERVIEW
1
MEASURED VALUES
UNDERVOLTAGE MONITORING
REQ’D VOLTAGE:
>
20 V applied in all phases
PICKUP:
0.50 to 0.99 in steps of 0.01
×
VT
DROPOUT:
103% of pickup
TIME DELAY:
0.5 to 600.0 in steps of 0.5 sec.
PHASES:
Any 1 / Any 2 / All 3 (programmable)
have to be
≤
pickup to operate
ACCURACY:
Per voltage input
TIMING ACCURACY: –0 / +1 sec.
OVERVOLTAGE MONITORING
PICKUP:
1.01 to 1.25 in steps of 0.01
×
VT
DROPOUT:
97% of pickup
TIME DELAY:
0.5 to 600.0 in steps of 0.5 sec.
PHASES:
Any 1 / Any 2 / All 3 (programmable)
must be
≥
pickup to operate
ACCURACY:
Per voltage input
TIMING ACCURACY: –0 / +1 sec.
UNDERFREQUENCY MONITORING
REQ’D VOLTAGE:
>
30 V applied in phase A
PICKUP:
20.00 to 70.00 in steps of 0.01 Hz
DROPOUT:
0.03 Hz
TIME DELAY:
0.1 to 10.0 in steps of 0.1 sec.
ACCURACY:
0.02 Hz
TIMING ACCURACY: ±3 cycles
OVERFREQUENCY MONITORING
REQ’D VOLTAGE:
>
30 V applied in phase A
PICKUP:
20.00 to 70.00 in steps of 0.01 Hz
DROPOUT:
Pickup – 0.03 Hz
TIME DELAY:
0.0 to 10.0 in steps of 0.1 sec.
ACCURACY:
0.02 Hz
TIMING ACCURACY: ±3 cycles
POWER FACTOR MONITORING
REQ’D VOLTAGE:
>
20 V applied in phase A
PICKUP:
0.50 lag to 0.50 lead step 0.01
DROPOUT:
0.50 lag to 0.50 lead step 0.01
TIME DELAY:
0.5 to 600.0 in steps of 0.5 sec.
TIMING ACCURACY: –0 / +1 sec.
DEMAND MONITORING
MEASURED VALUES:Phase A/B/C/N Current (A)
3
φ
Real Power (kW)
3
φ
Reactive Power (kvar)
3
φ
Apparent Power (kVA)
MEASUREMENT TYPE:
Thermal Exponential 90% response time
(programmable): 5 to 60 min. step 1
Block interval:
(programmable): 5 to 60 min. step 1
Rolling Demand
time interval:
(programmable): 5 to 60 min. step 1
PICKUP:
A: 10 to 7500 in steps of 1000
kW: 0.1 to 6500.0 in steps of 0.1
kvar: 0.1 to 6500.0 in steps of 0.1
kVA: 0.1 to 6500.0 in steps of 0.1
PULSE OUTPUT
PARAMETERS:
+kWh, –kWh, +kvarh, –kvarh, kVAh
INTERVAL:
1 to 65000 in steps of 1
PULSE WIDTH:
100 to 2000 ms in steps of 10 ms
MIN. PULSE INTERVAL: 500 ms
ACCURACY:
±
10 ms
PULSE INPUT
MAX INPUTS:
4
MIN PULSE WIDTH: 150 ms
MIN OFF TIME:
200 ms
PARAMETER
ACCURACY
(% of full scale)
RANGE
VOLTAGE
±0.2%
20% to 100% of VT
CURRENT
±0.2%
1% to 150% of CT
V UNBALANCE
±1%
0 to 100%
I UNBALANCE
±1%
0 to 100%
kW
see Accuracy Details 0 to ±999,999.99 kW
kvar
see Accuracy Details 0 to ±999,999.99 kvar
kVA
see Accuracy Details 0 to 999,999.99 kVA
kWh
see Accuracy Details 2
32
kWh
kvarh
see Accuracy Details 2
32
kvarh
kVAh
see Accuracy Details 2
32
kVAh
PF
±1.0%
±0.00 to 1.00
FREQUENCY
±0.02Hz
20.00 to 70.00 Hz
kW DEMAND
±0.4%
0 to ±999 999.99 kW
kvar DEMAND
±0.4%
0 to ±999 999.99 kvar
kVA DEMAND
±0.4%
0 to 999 999.99 kVA
AMP DEMAND
±0.2%
0 to 7500 A
AMPS THD
±2.0%
0.0 to 100.0%
VOLTS THD
±2.0%
0.0 to 100.0%
CREST FACTOR
±0.4%
1 to 9.99
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...