7 MODBUS COMMUNICATIONS
7.3 MODBUS MEMORY MAP
7
METER ID
continued
1004
Meter ID characters 9 and 10
tototo
---
ASCII
F10
N/A
1005
Meter ID characters 11 and 12
tototo
---
ASCII
F10
N/A
1006
Meter ID characters 13 and 14
tototo
---
ASCII
F10
N/A
1007
Meter ID characters 15 and 16
tototo
---
ASCII
F10
N/A
1008
Meter ID characters 17 and 18
tototo
---
ASCII
F10
N/A
1009
Meter ID characters 19 and 20
tototo
---
ASCII
F10
N/A
100A
Reserved
to
↓
↓
↓
↓
↓
↓
100F
Reserved
PREFERENCES
1010
Default Message Time
1 to 1201***
1
min x0.1
F1
10 = 1.0 min
1011
Default Message Brightness
0 to 100
20
%
F1
60 %
1012
Display Filter Constant
1 to 10
1
---
F1
4
1013
Reserved
to
↓
↓
↓
↓
↓
↓
1017
Reserved
RS485 COM1
SERIAL PORT
1018
Serial Communication Address
1 to 255
1
---
F1
1
1019
Modbus Baud Rate for RS485 COM1
0 to 4
1
---
F12
3 = 9600
101A
Parity for RS485 COM1
0 to 2
1
---
F13
0 = NONE
101B
Reserved
to
↓
↓
↓
↓
↓
↓
101F
Reserved
RS485 COM2
SERIAL PORT
1020
Modbus Baud Rate for RS485 COM2
0 to 4
1
---
F12
3 = 9600
1021
Parity for RS485 COM2
0 to 2
1
---
F13
0 = NONE
1022
Reserved
to
↓
↓
↓
↓
↓
↓
1027
Reserved
RS232
SERIAL PORT
1028
Modbus Baud Rate for RS232
0 to 4
1
---
F12
3 = 9600
1029
Parity for RS232
0 to 2
1
---
F13
0 = NONE
102A
Reserved
to
↓
↓
↓
↓
↓
↓
102F
Reserved
CALCU-
LATION
PARAMETERS
1030
Current Demand Calculation Type
0 to 2
1
---
F28
0 = Block Interval
1031
Current Demand Time Interval
5 to 180
1
minutes
F1
30 min
1032
Power Demand Calculation Type
0 to 2
1
---
F28
0 = Block Interval
1033
Power Demand Time Interval
5 to 180
1
minutes
F1
30 min
1034
Energy Cost Per kWh
1 to 50000
1
¢ x 0.01
F1
10.00 ¢
1035
Extract Fundamental
0 to 1
1
---
F11
0=DISABLE
1036
Reserved
1037
Reserved
CLEAR DATA
1038
Clear Energy Values
0 to 1
1
---
F31
0 = NO
1039
Clear Max Demand Values
0 to 1
1
---
F31
0 = NO
103A
Clear Min/Max Current Values
0 to 1
1
---
F31
0 = NO
103B
Clear Min/Max Voltage Values
0 to 1
1
---
F31
0 = NO
103C
Clear Min/Max Power Values
0 to 1
1
---
F31
0 = NO
Table 7–10: PQM MEMORY MAP (Sheet 27 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...