GE Power Management
PQM Power Quality Meter
5-17
5 MONITORING
5.2 A1 METERING
5
5.2.8 PULSE COUNTER
Figure 5–10: ACTUAL VALUES PAGE 1 – METERING / PULSE COUNTER
PULSE INPUT 1: This message displays the accumulated value based on total number of pulses counted
since the last reset. One switch input pulse is equal to the value assigned in the
S2 SYSTEM SETUP \ PULSE
INPUT \ PULSE INPUT 1 VALUE
setpoint. The units shown after the value are as defined in the
S2 SYSTEM
SETUP \ PULSE INPUT \ PULSE INPUT UNITS
setpoint. The displayed value will roll over to 0 once the value
4294967295 (FFFFFFFFh) has been reached. To use this feature, the “C” (control) option must be installed
and one of the PQM switch inputs must be assigned to PULSE INPUT 1 function. The switch input will then
count the number of closures or openings depending upon how the switch is configured. See setpoints page
S2 SYSTEM SETUP \ SWITCH INPUT A/B/C/D
for details on programming the switch inputs. The minimum timing
requirements are shown below in Figure 5.11.
PULSE INPUT 2: See the
PULSE INPUT 1
description above and replace all references to
PULSE INPUT 1
with
PULSE INPUT 2
.
PULSE INPUT 3: See the
PULSE INPUT 1
description above and replace all references to
PULSE INPUT 1
with
PULSE INPUT 3
.
PULSE INPUT 4: See the
PULSE INPUT 1
description above and replace all references to
PULSE INPUT 1
with
PULSE INPUT 4
.
PULSE IN 1+2+3+4: The totalized pulse input value is displayed here. The pulse inputs totalized is based on
the
S2 SYSTEM SETUP \ PULSE INPUT \ PULSE INPUT TOTAL
setpoint.
]] ACTUAL VALUES
]] A1 METERING
] PULSE COUNTER
]
PULSE INPUT 1 =
0 Units
PULSE INPUT 2 =
0 Units
PULSE INPUT 3 =
0 Units
]] ACTUAL VALUES
]] A2 STATUS
ACTUAL
PULSE INPUT 4 =
0 Units
PULSE INPUT 1+2+3+4
= 0 Units
TIME OF LAST RESET:
12:00:00am
01/01/95
M E S S A G E
M E S S A G E
M E S S A G E
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...