GE Power Management
PQM Power Quality Meter
7-55
7 MODBUS COMMUNICATIONS
7.3 MODBUS MEMORY MAP
7
7.3.4 MEMORY MAP DATA FORMATS
Table 7–11: MEMORY MAP DATA FORMATS (Sheet 1 of 16)
CODE
DESCRIPTION
BITMASK
F1
UNSIGNED INTEGER - NUMERICAL DATA
FFFF
F2
SIGNED INTEGER - NUMERICAL DATA
FFFF
F3
UNSIGNED LONG INTEGER - NUMERICAL DATA
FFFFFFFF
F4
SIGNED LONG INTEGER - NUMERICAL DATA
FFFFFFFF
F5
HARDWARE VERSION CODE
FFFF
1 = A
---
2 = B
---
↓
Ø
26 = Z
---
F6
UNSIGNED INTEGER - CURRENT KEY PRESS
FFFF
0000 = no key
---
FE01 = STORE
---
FE02 = SETPOINT
---
FE04 = MESSAGE RIGHT
---
FE08 = VALUE UP
---
FD01 = RESET
---
FD02 = MESSAGE LEFT
---
FD04 = MESSAGE UP
---
FD08 = VALUE DOWN
---
FB01 = ACTUAL
---
FB02 = MESSAGE DOWN
---
F7
UNSIGNED INTEGER - COMMAND
FFFF
1 = Reset
---
2 = Alarm Relay On
---
3 = Alarm Relay Off
---
4 = Auxiliary Relay 1 On
---
5 = Auxiliary Relay 1 Off
---
6 = Auxiliary Relay 2 On
---
7 = Auxiliary Relay 2 Off
---
8 = Auxiliary Relay 3 On
---
9 = Auxiliary Relay 3 Off
---
10 = Set Clock Time
---
11 = Set Clock Date
---
12 = Display 40 character Flash Message for 5 s
---
13 = Simulate Keypress
---
14 = Clear Energy Values
---
15 = Clear Max. Demand Values
---
16 = Clear Min./Max. Current Values
---
17 = Clear Min./Max. Voltage Values
---
18 = Clear Min./Max. Power Values
---
19 = Clear Max. THD Values
---
20 = Clear Switch Input Pulse Count
---
21 = High Speed Sampling Trigger
---
22 = Upload Mode Entry 2
---
23 = Upload Mode Entry 1
---
F7
con’t
24 = Factory Setpoints Reload 2
---
25 = Factory Setpoints Reload 1
---
26 = Test Relays and LEDs
---
27 = Waveform Capture Trigger
---
28 = Start Data Log(s)
---
29 = Stop Data Log(s)
---
30 = Resize Data Logs
(valid only if both logs are stopped)
---
31 = Clear Event Record
---
32= Trigger Trace Memory
---
33= Re-arm Trace Memory
---
34= Clear All Demand
---
35= Clear Min./Max. Frequency
---
F8
UNSIGNED INTEGER - KEYPRESS SIMULATION
FFFF
49 = '1' = SETPOINT
---
50 = '2' = ACTUAL
---
51 = '3' = RESET
---
52 = '4' = STORE
---
53 = '5' = MESSAGE UP
---
54 = '6' = MESSAGE DOWN
---
55 = '7' = MESSAGE LEFT
---
56 = '8' = MESSAGE RIGHT
---
57 = '9' = VALUE UP
---
97 = 'a' = VALUE DOWN
---
F9
UNSIGNED INTEGER - RELAY/LED TEST DATA
FFFF
Alarm Relay
0001
Auxiliary Relay 1
0002
Auxiliary Relay 2
0004
Auxiliary Relay 3
0008
‘ALARM’ LED
0010
‘PROGRAM’ LED
0020
‘SIMULATION’ LED
0040
‘SELF TEST’ LED
0080
‘ALARM’ Relay LED
0100
‘AUX 1’ Relay LED
0200
‘AUX 2’ Relay LED
0400
‘AUX 3’ Relay LED
0800
F10
TWO ASCII CHARACTERS
FFFF
32-127 = ASCII Character
7F00
32-127 = ASCII Character
007F
F11
UNSIGNED INTEGER - ENABLE/DISABLE
FFFF
0 = Disable/OFF
---
1 = Enable/ON
---
Table 7–11: MEMORY MAP DATA FORMATS (Sheet 2 of 16)
CODE
DESCRIPTION
BITMASK
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...