7-42
PQM Power Quality Meter
GE Power Management
7.3 MODBUS MEMORY MAP
7 MODBUS COMMUNICATIONS
7
CLEAR DATA
continued
103D
Clear Max THD Values
0 to 1
1
---
F31
0 = NO
103E
Clear Pulse Input Values
0 to 1
1
---
F31
0 = NO
103F
Clear Event Record
0 to 1
1
---
F31
0 = NO
1040
Clear All Demand Values
0 to 1
1
---
F31
0 = NO
1041
Clear Frequency Values
0 to 1
1
---
F31
0 = NO
1042
Reserved
1043
Reserved
DNP
1044
DNP Port
0 to 3
1
---
F47
0 = NONE
1045
DNP Slave Address
0 to 255
1
---
F1
0
1046
DNP Turnaround Time
0 to 100
10
ms
F1
10 ms
TARIFF
1047
Tariff Period 1 Start Time
0 to 1439
1
minutes
F1
0 min.
1048
Tariff Period 1 Cost per MWh
1 to 50000
1
¢
×
0.01
F1
10.00 ¢
1049
Tariff Period 2 Start Time
0 to 1439
1
minutes
F1
0 min.
104A
Tariff Period 2 Cost per MWh
1 to 50000
1
¢
×
0.01
F1
10.00 ¢
104B
Tariff Period 3 Start Time
0 to 1439
1
minutes
F1
0 min.
104C
Tariff Period 3 Cost per MWh
1 to 50000
1
¢
×
0.01
F1
10.00 ¢
104D
Reserved
104E
Reserved
104F
Reserved
CURRENT
/VOLTAGE
CONFIG.
1050
Phase CT Primary
0 to 12000
****
5
A
F1
100 A
1051
Neutral Current Sensing
0 to 2
1
---
F16
0 = OFF
1052
Neutral CT Primary
5 to 6000
5
A
F1
100 A
1053
VT Wiring
0 to 6
1
---
F15
0 = OFF
1054
VT Ratio
10 to 35000
1
0.1 xratio
F1
1.0:1
1055
VT Nominal Secondary Voltage
40 to 600
1
V
F1
120 V
1056
Nominal Direct Input Voltage
40 to 600
1
V
F1
600 V
1057
Nominal Frequency
50 to 60
10
Hz
F1
60 Hz
1058
CT Wiring
0 to 3
1
---
F44
0=A,B AND C
1059
Reserved
to
↓
↓
↓
↓
↓
↓
105F
Reserved
ANALOG
OUTPUT 1
1060
Analog Output 1 Main Type
0 to 59
1
---
F14
0=NOT USED
1061
Analog Output 1 Main Min Value
See Analog Output Range Table on page 7–63
0
1062
Analog Output 1 Main Max Value
See Analog Output Range Table on page 7–63
0
1063
Analog Output 1 Alternate Type
0 to 59
1
---
F14
0=NOT USED
1064
Analog Output 1 Alternate Min Value
See Analog Output Range Table on page 7–63
0
1065
Analog Output 1 Alternate Max Value
See Analog Output Range Table on page 7–63
0
1066
Reserved
1067
Analog Output 1 Serial Value
1
---
F2
0
ANALOG
OUTPUT 2
1068
Analog Output 2 Main Type
0 to 59
1
---
F14
0=NOT USED
1069
Analog Output 2 Main Min Value
See Analog Output Range Table on page 7–63
0
106A
Analog Output 2 Main Max Value
See Analog Output Range Table on page 7–63
0
106B
Analog Output 2 Alternate Type
0 to 59
1
---
F14
0=NOT USED
106C
Analog Output 2 Alternate Min Value
See Analog Output Range Table on page 7–63
0
Table 7–10: PQM MEMORY MAP (Sheet 28 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...