Instruction for Use

Superstatic 749

Summary of Contents for Superstatic 749

Page 1: ...Instruction for Use Superstatic 749 ...

Page 2: ... mounting of the calculator 11 5 3 Mounting of temperature sensors 12 5 4 Sensor pockets overview 13 5 5 Direct mounting in a T tube 13 5 6 Fitting temperature sensor for cooling application 14 6 Installation 14 6 1 Superstatic 749 14 6 2 Mounting of the for the pulse input function 14 6 3 Mounting cable for the pulse output function 14 7 Commissioning 15 7 1 Commissioning from the storage mode 15...

Page 3: ...erstatic 749 will be explained as a note in the current manual s different sections 1 2 Target groups This documentation is intended for the system operator and the installer 1 3 Storage of the document The system operator must ensure that this documentation is accessible to the responsible persons at all times If the original document is lost you can download an up to date version of this documen...

Page 4: ...ning the non observance of which may result in damage to property Reference Information that is important for a specific topic or goal but not relevant to security Documentation Reference to documentation Help Help in case of problems Visual check Check that the item is in order CE and UKCA Marking The device meets the requirements of the European directives and of the UK Conformity Assessment Dis...

Page 5: ...ergy meter Superstatic 749 is a precision measuring instrument approved for individual metering of heating systems and must be handled with care The Superstatic 749 is available in a heating or cooling or heating cooling version and determines the thermal and or cold energy exchanged by a heat bearing fluid in a heat exchanger circuit The Superstatic 749 complies with the requirements of the Europ...

Page 6: ...erating fluids n Action must be taken to ensure that no condensation water can penetrate inside the calculator n If there is any risk of vibrations the calculator must be installed separately on the wall n If the temperature of the fluid within the flow meter regularly reaches 90 C the calculator must be installed separately from the flow meter n It is advisable to drain the installation before fi...

Page 7: ...7 Instruction for use Superstatic 749 3 Scope of delivery Transport Storage Cleaning ...

Page 8: ... Superstatic 749 4 Superstatic 749 thermal energy meter 4 1 Dimension qp0 6 m3 h L 110 mm 86 8 110 2 L 52 78 D 105 87 5 35 5 53 57 2 L 86 8 89 110 2 78 D 110 5 35 5 57 2 53 54 49 90 4 2 Dimension qp1 5 m3 h L 130 or 190 mm ...

Page 9: ...9 Instruction for use Superstatic 749 4 Superstatic 749 thermal energy meter 4 3 Dimension qp2 5 m3 h L 130 or 190 mm L D 108 35 5 89 78 110 2 54 6 55 6 52 87 5 ...

Page 10: ...y interfering influence Waterproof will be checked at the various mounting points The heat conveying liquid must be equivalent to water without any additives according to standard FW510 of the AGFW German District Heating Association If additives are added to the water the user must ensure the compatibility of the materials used in the thermal energy meter which are in contact with these additives...

Page 11: ...rom the flow meter press laterally with one hand on the two locking buttons while pulling the calculator upwards Figure 2 Fix the calculator onto the wall fixing component taking care not to jam the cable which connects the calculator to the flow meter and stick the adhesive tab behind the wall component Secure the assembly to the wall Figure 3 Figure 1 Figure 2 Figure 3 To remove the calculator f...

Page 12: ... nut halves may separate from the temperature sensor 1 Remove the O ring from the temperature sensor Be careful not to remove the rubber band symbolized by the letter E on the drawing from the nut as it may separate into two parts and fall on the floor 2 Fit the O ring on the mounting template pin 3 Insert the O ring by rotating it using the fitting template in the position provided for the ball v...

Page 13: ...ng Ø 5 Pt1000 M10x1 SCTW4A1 Brass 0 100 C Ø 5 Pt1000 G3 8 SCTW4A2 Brass 0 100 C Ø 5 Pt1000 G1 2 SCTW4A3 Brass 0 100 C Ø 5 2 Pt1000 M10x1 SCTW4A4 Brass 0 100 C Ø 5 2 Pt1000 G3 8 SCTW4A5 Brass 0 100 C Ø 5 2 Pt1000 G1 2 SCTW4A6 Brass 0 100 C Ø 6 Pt1000 G1 2 SCTW1A1 Brass 0 100 C The temperature sensor is on the same level and perpendicular to the pipe axis DN15 DN20 5 4 Sensor pocket overview 5 5 Dir...

Page 14: ...e sure that the gaskets are carefully positioned in relation to the water pipe and flow meter unions Tighten the fixing nuts firmly by hand Then tighten up to the mechanical end stop using a mounting tool Install the temperature sensor Turn the display into the desired position for reading Check the waterproof of the meter placed under pressure Seal the flow meter and the temperature sensors 6 2 M...

Page 15: ...ngue PUSH CHANGE Long pression Automatic change 000000 01 MWh Short pression PUSH CHANGE Long pression Automatic change 000000 01 m3 Short pression PUSH CHANGE Long pression Automatic change Short pression Cold pipe Short pression 001234 56 MWh Energy Service Counting OFF Short pression Short Pression In the Config menu optionally available a long press will change the settings below Flow meter mo...

Page 16: ...9 software via the optical interface 8 Error codes The Superstatic 749 calculator displays an error message with the 3 letters Err and a code If several errors occur at the same time the different codes are added together The error is displayed in the first position of the display menu It will still be possible to select all the other display menus by pressing the navigation button If the navigati...

Page 17: ...Actual flow Aktuelle Leistung Puissance actuelle Actual power Segmenttest Test des segments Test LCD Identifikationsnummer Numéro d identification Identification number M Bus Adresse Adresse M Bus M Bus address Radio Adresse Adresse Radio Radio address Firmwareversion Version Firmware Firmware Version Energie Tariff 1 Monat 2 Energie Tariff 1 au mois 2 Energy Tariff 1 month 2 Letzter Monastwert En...

Page 18: ...ng energy Whenever the smallest energy unit hot or and cold or volume displayed on the screen is incremented 1 pulse will be transmitted on the corresponding output cable S1 S2 Example for energy Display 12345678 kWh output pulse value for energy 1 kWh pulse Display 12345 678 MWh output pulse value for energy 0 001 MWh pulse Display 123456 78 GJ output pulse value for energy 0 01 GJ pulse Example ...

Page 19: ... transfer data according to the wM Bus EN13757 4 radio communication protocol and in compliance with the OMS Open Metering System Release V4 To have this interface provided in the Superstatic 749 it is necessary to specify when ordering The Wireless M bus module will be installed and configured at the factory A specific notice will be added to the standard documentation Technical data Unidirection...

Page 20: ...col compliant with standard EN 1434 3 free potential interfacing without polarity the voltage measured on the last device must exceed 36VDC transmission speed 300 2400 Baud variable data structure A M bus device is seen as two M Bus charges by the Master Type of cable recommended telephone cable JYStY N 2 0 8 mm2 11 Security seals As sealing varies from country to country local regulations must be...

Page 21: ...0 130 Brass 16 3 0 15 10 yes 1 4 3 4 0 20 1 5 1 20 190 Brass 16 3 0 15 10 yes 1 6 3 4 0 20 2 5 1 20 130 Brass 16 5 0 25 17 yes 1 4 5 7 0 19 2 5 1 20 190 Brass 16 5 0 25 17 yes 1 6 5 7 0 19 16 bar 1 6 MPa Mounting The Superstatic 749 should not be mounted on the side where the continuous operating temperature of the liquid exceeds 90 C or is below 5 C Length of straight section fitted upstream down...

Page 22: ...ume or pulses C K Power supply 3 VDC Lithium Battery 6 1 or 12 1 years Radio communication Sontex Radio Frequency Communication Protocol Encryption Transmission power Transmission interval wM Bus Frequency Communication Protocol Encryption Transmission power Transmission interval LoRaWAN Frequency Communication Protocol Encryption Transmission power Transmission interval Uplink Downlink 433 82 MHz...

Page 23: ...ic 749 13 Declaration of Conformity Sontex hereby declares that the Superstatic 749 complies with MID 2014 32 EU and RED 2014 53EU and with the UK Conformity Assessment The Declaration of Conformity are available at the following link ...

Page 24: ...1 32 488 30 00 sontex sontex ch www sontex ch 22 12 Technical support For technical support contact your local Sontex agent or Sontex SA directly Hotline Sontex support sontex ch 41 32 488 30 04 Technical modifications subject to change without notice ...