8-14
PQM Power Quality Meter
GE Power Management
8.1 DNP 3.0 PROTOCOL
8 DNP COMMUNICATIONS
8
8.1.8 POINT LIST FOR COUNTERS
Only counter points 0 to 4 can be cleared using function codes 9 and 10, and doing so disturbs the
totals presented on the display and via Modbus communications. In general, the binary output points
which clear data should be used if it is necessary to clear any of these counters.
Point list for: Binary Counters (object 20)
Frozen Counters (object 21)
Counter Change Event (object 22)
Frozen Counter Events (object 23)
Point
Num
Modbus
Register
Description
Unit
Deadband
Format
code
Event class point
assigned to
0
0450
Pulse Input 1
-
-
F3
-
1
0452
Pulse Input 2
-
-
F3
-
2
0454
Pulse Input 3
-
-
F3
-
3
0456
Pulse Input 4
-
-
F3
-
4
0460
Totalized Pulse Input
-
-
F3
-
5
03D0
3 Phase Positive Real Energy
Used
kWh
-
F3
-
6
03D2
3 Phase Negative Real Energy
Used
kWh
-
F3
-
7
03D4
3 Phase Positive React.
Energy Used
kvarh
-
F3
-
8
03D6
3 Phase Negative React.
Energy Used
kvarh
-
F3
-
9
03D8
3 Phase Apparent Energy
Used
kVAh
-
F3
-
10
03DA
3 Phase Energy Used in Last
24 h
kWh
-
F3
-
11
03DC
3 Phase Energy Cost Since
Reset
cents
-
F3
-
12
03DE
3 Phase Energy Cost Per Day
cents
-
F3
-
NOTE
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...