5-22
PQM Power Quality Meter
GE Power Management
5.3 A2 STATUS
5 MONITORING
5
Figure 5–13: ACTUAL VALUES PAGE 2 – STATUS / ALARMS
The alarm messages appear only when the alarm threshold has been exceeded for the programmed time.
When an alarm is assigned to an output relay, the relay can be set to be unlatched or latched. When the alarm
is set as unlatched, it automatically resets when the alarm condition no longer exists. If the alarm is set as
latched, a keypad reset or a serial port reset is required.
The
SELF TEST ALARM
occurs if a fault in the PQM hardware is detected. This alarm is permanently
assigned to the alarm output relay and is not user configurable. If this alarm is present, contact the
GE Power Management Service Department.
5.3.2 SWITCH STATUS
Figure 5–14: ACTUAL VALUES PAGE 2 – SWITCH STATUS
SWITCH INPUT A/B/C/D STATE: To assist in troubleshooting, the state of each switch can be verified using
these messages. A separate message displays the status of each input identified by the corresponding name
as shown in the wiring diagrams in chapter 2. For a dry contact closure across the corresponding switch termi-
nals the message will read
CLOSED
.
PULSE INPUT 1
ALARM
PULSE INPUT 2
ALARM
PULSE INPUT 3
ALARM
PULSE INPUT 4
ALARM
TOTALIZED PULSES
ALARM
TIME
ALARM
M E S S A G E
M E S S A G E
CONTINUED FROM
PREVIOUS PAGE
NOTE
]] ACTUAL VALUES
]] A2 STATUS
] SWITCHES
]
SWITCH INPUT A
STATE: CLOSED
SWITCH INPUT B
STATE: CLOSED
SWITCH INPUT C
STATE: CLOSED
SWITCH INPUT D
STATE: CLOSED
]] ACTUAL VALUES
]] A3 POWER ANALYSIS
ACTUAL
M E S S A G E
M E S S A G E
M E S S A G E
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...