7-50
PQM Power Quality Meter
GE Power Management
7.3 MODBUS MEMORY MAP
7 MODBUS COMMUNICATIONS
7
PULSE
INPUT
ALARMS
11B8
Pulse Input 2 Relay
0 to 4
1
---
F29
0=OFF
11B9
Pulse Input 2 Level
1 to 65000
1
---
F1
100
11BA
Pulse Input 2 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11BB
Pulse Input 3 Relay
0 to 4
1
---
F29
0=OFF
11BC
Pulse Input 3 Level
1 to 65000
1
---
F1
100
11BD
Pulse Input 3 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11BE
Pulse Input 4 Relay
0 to 4
1
---
F29
0=OFF
11BF
Pulse Input 4 Level
1 to 65000
1
---
F1
100
11C0
Pulse Input 4 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11C1
Totalized Pulse Input Relay
0 to 4
1
---
F29
0=OFF
11C2
Totalized Pulse Input Level
1 to 65000
1
---
F1
100
11C3
Totalized Pulse Input Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11C4
Reserved
to
↓
↓
↓
↓
↓
↓
11C7
Reserved
SIMULATION
11C8
Current/Voltage Simulation
0 to 1
1
---
F11
0=OFF
11C9
Current/Voltage Simulation Time
5 to 305
5
min
F1
*****
15 min
11CA
Phase A Current
0 to 10000
1
A
F1
0 A
11CB
Phase B Current
0 to 10000
1
A
F1
0 A
11CC
Phase C Current
0 to 10000
1
A
F1
0 A
11CD
Neutral Current
0 to 10000
1
A
F1
0 A
11CE
Vax Voltage
0 to 65000
1
V
F1
0 V
11CF
Vbx Voltage
0 to 65000
1
V
F1
0 V
11D0
Vcx Voltage
0 to 65000
1
V
F1
0 V
11D1
Phase Angle
0 to 359
1
degrees
F1
0 degrees
11D2
Analog Output Simulation
0 to 1
1
---
F11
0=OFF
11D3
Analog Output Simulation Time
5 to 305
5
min
F1
*****
15 min
11D4
Analog Output 1
0 to 1201***
1
0.1 x %
F1
1201=OFF
11D5
Analog Output 2
0 to 1201***
1
0.1 x %
F1
1201=OFF
11D6
Analog Output 3
0 to 1201***
1
0.1 x %
F1
1201=OFF
11D7
Analog Output 4
0 to 1201***
1
0.1 x %
F1
1201=OFF
11D8
Analog Input Simulation
0 to 1
1
---
F11
0=OFF
11D9
Analog Input Simulation Time
5 to 305
5
min
F1
*****
15 min
11DA
Analog Input
40 to 201
1
0.1 x mA
F1
201=OFF
11DB
Switch Input Simulation
0 to 1
1
---
F11
0=OFF
11DC
Switch Input Simulation Time
5 to 305
5
min
F1
*****
15 min
11DD
Switch Input A
0 to 1
1
---
F27
0=OPEN
11DE
Switch Input B
0 to 1
1
---
F27
0=OPEN
11DF
Switch Input C
0 to 1
1
---
F27
0=OPEN
11E0
Switch Input D
0 to 1
1
---
F27
0=OPEN
11E1
Reserved
11E2
Reserved
11E3
Reserved
Table 7–10: PQM MEMORY MAP (Sheet 36 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...