4-26
PQM Power Quality Meter
GE Power Management
4.3 S2 SYSTEM SETUP
4 PROGRAMMING
4
•
ANALOG IN MAIN/ALT SELECT RELAY: Select the output relay that is to be used to multiplex two analog
input signals to the PQM. If this setpoint is
OFF
, the MAIN analog input setpoints will be used unless a
switch input assigned to SELECT ANALOG INPUT is activated. For more information on multiplexing two
analog inputs using one of the PQM output relays, refer to Section 2.2.6: SWITCH INPUTS (OPTIONAL)
on page 2–15.
•
ANALOG IN MAIN/ALT NAME: This message allows the user to input a user defined 20 character alpha-
numeric name for the MAIN and ALT analog inputs. To enter the names, perform the following steps:
1.
Allow access to setpoints by enabling setpoint access.
2.
Select the Analog Input name message display under the
S2 SYSTEM SETUP \ ANALOG INPUT
setpoints
group.
3.
Use the
and
keys to change the blinking character over the cursor. A space is
selected like a character.
4.
Press the
key to store the character and advance the cursor to the next position. To skip over
a character press the
key.
5.
Continue entering characters and spaces until the desired message is displayed. If a character is
entered incorrectly, press the
key repeatedly until the cursor returns to the position of the
error, and re-enter the character.
•
ANALOG IN MAIN/ALT UNITS: This message allows the user to input a user defined 10 character alpha-
numeric name for the MAIN and ALT units. To enter the units, perform the same steps as shown for analog
input name.
•
MAIN/ALT 4 mA VALUE: This message appears for each analog input and allows the user to assign a
numeric value which corresponds to the 4 mA end of the 4 to 20 mA signal range.
•
MAIN/ALT 20 mA VALUE: This message appears for each analog input and allows the user to assign a
numeric value which corresponds to the 20 mA end of the 4 to 20 mA signal range.
•
ANALOG IN MAIN/ALT RELAY: Analog input MAIN and ALT detection can either be disabled, used as an
alarm or as a process control. Set this setpoint to
OFF
if the feature is not required. Selecting
ALARM
causes
the alarm relay to activate and displays an alarm message whenever a MAIN or ALT analog input condition
exists. Selecting an
AUXILIARY
relay causes the selected auxiliary relay to activate with no message dis-
played. This is intended for process control.
•
ANALOG IN MAIN/ALT LEVEL: When the measured MAIN or ALT analog input exceeds the level set by
this setpoint, a MAIN or ALT analog input condition will occur.
•
ANALOG IN MAIN/ALT DELAY: If the MAIN or ALT analog input exceeds the
ANALOG IN MAIN/ALT LEVEL
setpoint value and remains this way for the time delay programmed in this setpoint, an analog input condi-
tion will occur. If the
ANALOG IN MAIN/ALT RELAY:
setpoint is set to
ALARM
, the alarm relay will activate and
the
ANALOG IN MAIN/ALT ALARM
message will be displayed. If the setpoint
ANALOG IN MAIN/ALT RELAY:
is set
to
AUX1
,
AUX2
or
AUX3
the respective auxiliary relay will activate and no message will be displayed after the
delay expires.
V A L U E
V A L U E
S T O R E
S T O R E
S T O R E
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...