8.1.7 POINT LIST FOR ANALOG INPUT/OUTPUT CHANGE
In the following table, the entry in the “Format” column indicates that the format of the associated data point
can be determined by looking up the entry in Table 7–11: MEMORY MAP DATA FORMATS on page 7–55. For
example, an “F1” format is described in that table as a (16-bit) unsigned value without any decimal places.
Therefore, the value read should be interpreted in this manner
Table 8–1: POINT LIST FOR ANALOG INPUT/OUTPUT CHANGE (Sheet 1 of 5)
POINT
MOBUS
REG
DESCRIPTION
UNIT / VALUE
DEADBAND
FORMAT
CODE
EVENT CLASS
ASSIGNED TO
1
1050
Phase CT Primary setpoint
1
amps
1 unit
F1
3
2
1052
Neutral CT Primary setpoint
1
amps
1 unit
F1
3
3
1054
VT Ratio setpoint
2
0.1 x ratio
1 unit
F1
3
4
1055
VT Nominal Secondary Voltage
setpoint
volts
1 unit
F1
3
5
-
VT Nominal Phase-to-Phase
Voltage
3
(VT Ratio x Nominal Sec. adjusted
for wye or delta)
32-bit volts
1 unit
F3
3
6
-
VT Nominal Phase-to-Neutral
Voltage
(VT Ratio x Nominal Sec. adjusted
for wye or delta)
32-bit volts
1 unit
F3
3
7
-
Nominal Single-Phase VA
4
(VT Nominal Pri. x Phase CT Pri.)
32-bit VA
1 unit
F3
3
8
-
Nominal Three-Phase VA
(VT Nominal Pri. x Phase CT Pri. x
3)
32-bit VA
1 unit
F3
3
9
0240
Phase A Current
1000ths of nominal A
20 units
F1
1
10
0241
Phase B Current
1000ths of nominal
20 units
F1
1
11
0242
Phase C Current
1000ths of nominal
20 units
F1
1
12
0243
Average Current
1000ths of nominal
20 units
F1
1
13
0244
Neutral Current
1000ths of nominal
20 units
F1
1
14
0245
Current Unbalance
tenths of 1 percent
10 units
F1
2
15
0280
Voltage Van
1000ths of nominal V
20 units
F3
1
16
0282
Voltage Vbn
1000ths of nominal V
20 units
F3
1
17
0284
Voltage Vcn
1000ths of nominal V
20 units
F3
1
18
0286
Average Phase Voltage
1000ths of nominal V
20 units
F3
1
19
0288
Voltage Vab
1000ths of nominal V
20 units
F3
1
20
028A
Voltage Vbc
1000ths of nominal V
20 units
F3
1
21
028C
Voltage Vca
1000ths of nominal V
20 units
F3
1
22
028E
Average Line Voltage
1000ths of nominal
20 units
F3
1
23
0290
Voltage Unbalance
0.1 x %
10 units
F1
2
24
02F0
3 Phase Real Power
1000ths of nominal VA
20 units
F4
2
25
02F2
3 Phase Reactive Power
1000ths of nominal VA
20 units
F4
2
26
02F4
3 Phase Apparent Power
1000ths of nominal VA
20 units
F3
2
see footnote explanations at the end of the table
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...