GE Power Management
PQM Power Quality Meter
7-19
7 MODBUS COMMUNICATIONS
7.3 MODBUS MEMORY MAP
7
CURRENT
continued
0265
Time - Seconds of Phase A Current Max
---
---
---
F23
N/A
0266
Date - Month/Day of Phase A Current Max
---
---
---
F24
N/A
0267
Date - Year of Phase A Current Max
---
---
---
F25
N/A
0268
Time - Hour/Minutes of Phase B Curr. Max
---
---
---
F22
N/A
0269
Time - Seconds of Phase B Current Max
---
---
---
F23
N/A
026A
Date - Month/Day of Phase B Current Max
---
---
---
F24
N/A
026B
Date - Year of Phase B Current Max
---
---
---
F25
N/A
026C
Time - Hour/Minutes of Phase C Curr. Max
---
---
---
F22
N/A
026D
Time - Seconds of Phase C Current Max
---
---
---
F23
N/A
026E
Date - Month/Day of Phase C Current Max
---
---
---
F24
N/A
026F
Date - Year of Phase C Current Max
---
---
---
F25
N/A
0270
Time - Hour/Minutes of Neutral Current Max
---
---
---
F22
N/A
0271
Time - Seconds of Neutral Current Max
---
---
---
F23
N/A
0272
Date - Month/Day of Neutral Current Max
---
---
---
F24
N/A
0273
Date - Year of Neutral Current Max
---
---
---
F25
N/A
0274
Time - Hour/Minutes of Current Unbal. Max
---
---
---
F22
N/A
0275
Time - Seconds of Current Unbal. Max
---
---
---
F23
N/A
0276
Date - Month/Day of Current Unbal. Max
---
---
---
F24
N/A
0277
Date - Year of Current Unbalance Max
---
---
---
F25
N/A
0278
Reserved
to
↓
↓
↓
↓
↓
↓
027F
Reserved
VOLTAGE
0280
Voltage Van (High)
---
---
V
F3
N/A
0281
Voltage Van (Low)
---
---
V
F3
N/A
0282
Voltage Vbn (High)
---
---
V
F3
N/A
0283
Voltage Vbn (Low)
---
---
V
F3
N/A
0284
Voltage Vcn (High)
---
---
V
F3
N/A
0285
Voltage Vcn (Low)
---
---
V
F3
N/A
0286
Average Phase Voltage (High)
---
---
V
F3
N/A
0287
Average Phase Voltage (Low)
---
---
V
F3
N/A
0288
Voltage Vab (High)
---
---
V
F3
N/A
0289
Voltage Vab (Low)
---
---
V
F3
N/A
028A
Voltage Vbc (High)
---
---
V
F3
N/A
028B
Voltage Vbc (Low)
---
---
V
F3
N/A
028C
Voltage Vca (High)
---
---
V
F3
N/A
028D
Voltage Vca (Low)
---
---
V
F3
N/A
028E
Average Line Voltage (High)
---
---
V
F3
N/A
028F
Average Line Voltage (Low)
---
---
V
F3
N/A
0290
Voltage Unbalance
---
---
0.1 x %
F1
N/A
0291
Voltage Van - Minimum (high)
---
---
V
F3
N/A
0292
Voltage Van - Minimum (Low)
---
---
V
F3
N/A
0293
Voltage Vbn - Minimum (high)
---
---
V
F3
N/A
0294
Voltage Vbn - Minimum (Low)
---
---
V
F3
N/A
0295
Voltage Vcn - Minimum (high)
---
---
V
F3
N/A
Table 7–10: PQM MEMORY MAP (Sheet 5 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Содержание Power Quality Meter Series
Страница 2: ......
Страница 4: ......
Страница 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Страница 29: ...GE Power Management PQM Power Quality Meter 2 5 2 INSTALLATION 2 2 ELECTRICAL 2 Figure 2 3 REAR TERMINALS ...
Страница 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Страница 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Страница 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Страница 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Страница 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Страница 281: ...GE Power Management PQM Power Quality Meter NOTES ...